Plan Review Notes
Plan Review Notes For Permit 16070025
Permit Number 16070025
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-07-07 15:20:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A.1 - DOOR 114 IS INDICATED WITHIN A FIRE
 RATED WALL; HOWEVER, SHEET A..3, DOOR AND FRAME
 SCHEDULE INDICATES DOOR 114 AND HARDWARE AS HAVING NO
 RATING.
  
 PLEASE CORRECT OR CLARIFY.
  
 2) SHEET A.1 - KEYNOTE # 10 INDICATES A WINDOW WITHIN A
 FIRE RATED WALL; HOWEVER, THERE IS FIRE RATING
 INDICATED FOR THE WINDOW.
  
 PLEASE CORRECT OR JUSTIFY.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  