| 2016-07-11 15:32:39 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. PAGE. E1: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL |
| | 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES |
| | AND COMPUTER CLASSROOMS. THIS INCLUDES MODULAR |
| | PARTITIONS TOO. SHOW COMPLIANCE ACCORDINGLY. |
| | 2. PER NEC 408.4(A), A CIRCUIT DIRECTORY FOR EVERY |
| | PANEL IS REQUIRED. |
| | 3. PER NEC 408.4(B), ALL PANELS SHALL BE MARKED WITH |
| | THE LOCATION OF THE SOURCE OF POWER. WHILE OBN THIS |
| | TOPIC, THERE ARE MORE PANEL INDICATED ON THE FLOOR |
| | PLANS THAT APPEAR ON THE RISER DIAGRAM ON PAGE E3. |
| | 4. PAGE E2: PER FBC-EC405.2.2.3 ADDITIONAL LIGHTING |
| | CONTROL IS REQUIRED FOR DAYLIGHT ZONES. RECONFIGURE |
| | YOUR LIGHTING PLAN ACCORDINGLY. |
| | 5. PAGE E3: NEC 215.5 REQUIRES THAT YOU PROVIDE LOAD |
| | CALCS. INCLUDE ALL APPLICABLE PANELS. |
| | 6. NEC 230.2 RESTRICTS YOUR SERVICES TO ONE UNLESS |
| | SPECIFIC CONDITIONS ARE MET. EXPLAIN WHAT YOU MEAN BY |
| | SERVICE 4 OF 4 AND THEN STILL ANOTHER SERVICE AS |
| | EXISTING.. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |