2016-07-11 15:32:391ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. PAGE. E1: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL
 125V, 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES
 AND COMPUTER CLASSROOMS. THIS INCLUDES MODULAR
 PARTITIONS TOO. SHOW COMPLIANCE ACCORDINGLY.
 2. PER NEC 408.4(A), A CIRCUIT DIRECTORY FOR EVERY
 PANEL IS REQUIRED.
 3. PER NEC 408.4(B), ALL PANELS SHALL BE MARKED WITH
 THE LOCATION OF THE SOURCE OF POWER. WHILE OBN THIS
 TOPIC, THERE ARE MORE PANEL INDICATED ON THE FLOOR
 PLANS THAT APPEAR ON THE RISER DIAGRAM ON PAGE E3.
 4. PAGE E2: PER FBC-EC405.2.2.3 ADDITIONAL LIGHTING
 CONTROL IS REQUIRED FOR DAYLIGHT ZONES. RECONFIGURE
 YOUR LIGHTING PLAN ACCORDINGLY.
 5. PAGE E3: NEC 215.5 REQUIRES THAT YOU PROVIDE LOAD
 CALCS. INCLUDE ALL APPLICABLE PANELS.
 6. NEC 230.2 RESTRICTS YOUR SERVICES TO ONE UNLESS
 SPECIFIC CONDITIONS ARE MET. EXPLAIN WHAT YOU MEAN BY
 SERVICE 4 OF 4 AND THEN STILL ANOTHER SERVICE AS
 EXISTING..
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  