| 2016-07-19 14:59:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070025 |
| | ADD: 2450 METRO CENTRE BLVD. |
| | CONT: MEDICAL CONSULTANTS PLUS |
| | TEL: 954-444-3325 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 19/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 & LIFE SAFETY SHEET, PLEASE SHOW HOW MANY |
| | OCCUPANTS WILL BE IN THE SUB-WAITING AREA # 112? |
| | DEPENDING ON THE OCCUPANT LOAD IN THE CORRIDORS LEADING |
| | AWAY SOME OF THE CORRIDORS MAY REQUIRE A 1 HOUR FIRE |
| | RATING. SEE FBC-B TABLE 1018.1, BUSINESS OCCUPANCY WHEN |
| | THE CORRIDOR SERVES AN OCCUPANT LOAD GREATER THAN 30 IN |
| | A NON-SPRINKLERED BUILDING. |
| | |
| | 2) SHEET A.3 THE TOLIET GRAB BARS ARE SHOWN BEING |
| | MEASURED FROM THE CENTERLINE TO THE FINISH FLOOR. UNDER |
| | THE 2014 FBC-ACCESSIBILTY CODE SECTION 609.4 THEY ARE |
| | TO BE MEASURED FROM THE TOP OF THE GRIPPING SURFACE TO |
| | THE FINISH FLOOR. |
| | |
| | 3) SHEET A.5 DETAIL 1 SHOWS A MICROWAVE ON THE BOTTOM |
| | SHELF OF THE UPPER CABINETS. PLEASE REVIEW 2014 |
| | FBC-ACCESS. CODE REACH RANGES IN 308 AND OPERABLE PARTS |
| | UNDER 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED |
| | WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN |
| | 308. |
| | |
| | 4) SHEET M2 INDICATES THE USE OF NEW ROOF TOP A/C |
| | STANDS. PLEASE PROVIDE COMPLIANCE WITH 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS / WALL LOUVERS FOR |
| | OUTSIDE AIR. |
| | |
| | 5) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL |
| | IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR |
| | REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED |
| | BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL |
| | ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE |
| | BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | |
| | 6) DEPENDING ON THE PLACEMENT OF THE A/C STAND |
| | ADDITIONAL ROOF FRAMING RE-INFORCEMENT MAY BE NEEDED TO |
| | ANCHOR INTO THE MAIN WIND FORCE RESISTING SYSTEM |
| | (MWFRS). 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| | PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. 22014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | |
| | 7) PLEASE PROVIDE THE WIND DESIGN CRITERIA INCLUDING |
| | THE MEAN ROOF HEIGHT, EXPOSURE AND PRESSURES FOR THE |
| | NEW ROOFTOP A/C STAND AND ROOF TOP CONDENSING UNITS. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 8) PLEASE ALSO PROVIDE THE ANCHORING OF THE ROOF TOP |
| | UNITS TO THE NEW ROOF TOP STAND. 2014 FBC-M- 301.15 |
| | WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |