Plan Review Notes
Plan Review Notes For Permit 16070025
Permit Number 16070025
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-19 14:59:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070025
 ADD: 2450 METRO CENTRE BLVD.
 CONT: MEDICAL CONSULTANTS PLUS
 TEL: 954-444-3325
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 19/ 2016
 ACTION: DENIED
  
 1) SHEET A-1 & LIFE SAFETY SHEET, PLEASE SHOW HOW MANY
 OCCUPANTS WILL BE IN THE SUB-WAITING AREA # 112?
 DEPENDING ON THE OCCUPANT LOAD IN THE CORRIDORS LEADING
 AWAY SOME OF THE CORRIDORS MAY REQUIRE A 1 HOUR FIRE
 RATING. SEE FBC-B TABLE 1018.1, BUSINESS OCCUPANCY WHEN
 THE CORRIDOR SERVES AN OCCUPANT LOAD GREATER THAN 30 IN
 A NON-SPRINKLERED BUILDING.
  
 2) SHEET A.3 THE TOLIET GRAB BARS ARE SHOWN BEING
 MEASURED FROM THE CENTERLINE TO THE FINISH FLOOR. UNDER
 THE 2014 FBC-ACCESSIBILTY CODE SECTION 609.4 THEY ARE
 TO BE MEASURED FROM THE TOP OF THE GRIPPING SURFACE TO
 THE FINISH FLOOR.
  
 3) SHEET A.5 DETAIL 1 SHOWS A MICROWAVE ON THE BOTTOM
 SHELF OF THE UPPER CABINETS. PLEASE REVIEW 2014
 FBC-ACCESS. CODE REACH RANGES IN 308 AND OPERABLE PARTS
 UNDER 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 4) SHEET M2 INDICATES THE USE OF NEW ROOF TOP A/C
 STANDS. PLEASE PROVIDE COMPLIANCE WITH 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS / WALL LOUVERS FOR
 OUTSIDE AIR.
  
 5) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR
 REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED
 BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL
 ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE
 BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 6) DEPENDING ON THE PLACEMENT OF THE A/C STAND
 ADDITIONAL ROOF FRAMING RE-INFORCEMENT MAY BE NEEDED TO
 ANCHOR INTO THE MAIN WIND FORCE RESISTING SYSTEM
 (MWFRS). 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. 22014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 7) PLEASE PROVIDE THE WIND DESIGN CRITERIA INCLUDING
 THE MEAN ROOF HEIGHT, EXPOSURE AND PRESSURES FOR THE
 NEW ROOFTOP A/C STAND AND ROOF TOP CONDENSING UNITS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 8) PLEASE ALSO PROVIDE THE ANCHORING OF THE ROOF TOP
 UNITS TO THE NEW ROOF TOP STAND. 2014 FBC-M- 301.15
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  