| 2016-07-18 11:03:59 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070015 |
| | ADD: 801 S. OLIVE AVE. SUITE # 1601 |
| | CONT: GAST CONSTRUCTION |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 18/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE DEMOLITION PLANS INDICATE THE REMOVAL OF |
| | EXISITNG TILE FLOORING WITHIN THE UNIT. THE RENOVATION |
| | PLAN DOES NOT MENTION THE NEW FLOOR FINISHES WITHIN THE |
| | UNIT OR IF THERE ARE MULTIPLE FLOOR FINISHES. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2) THE PLANS ARE NOT CLEAR IN THE MASTER BATH THE |
| | SHOWER AND TUB WALLS ARE GOING TO BE REPLACED. IF SO |
| | THEN COMPLIANCE WITH THE 2014 FBC-B SECTION |
| | 2508.2 LIMITATIONS. GYPSUM WALLBOARD SHALL NOT BE USED |
| | IN ANY EXTERIOR SURFACE WHERE SUCH GYPSUM CONSTRUCTION |
| | WILL BE EXPOSED DIRECTLY TO THE WEATHER. GYPSUM |
| | WALLBOARD SHALL NOT BE USED WHERE THERE WILL BE DIRECT |
| | EXPOSURE TO CONTINUOUS HIGH HUMIDITY CONDITIONS. |
| | |
| | 2509.2 BASE FOR TILE. GLASS MAT WATER-RESISTANT GYPSUM |
| | BACKING PANELS, DISCRETE NONASBESTOS FIBER-CEMENT |
| | INTERIOR SUBSTRATE SHEETS OR NONASBESTOS FIBER-MAT |
| | REINFORCED CEMENTITIOUS BACKER UNITS IN COMPLIANCE WITH |
| | ASTM C 1178, C 1288 OR C 1325 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS SHALL BE |
| | USED AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS |
| | AND WALL AND CEILING PANELS IN SHOWER AREAS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A |
| | BASE FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840 AND |
| | MANUFACTURER RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD |
| | IS PERMITTED UNDER TILE OR WALL PANELS IN OTHER WALL |
| | AND CEILING AREAS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| | BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | 3) JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |