| 2016-07-05 18:39:14 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC, 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS (2 | | | COPIES) FOR THE ROOF REPAIRS AND GENERAL REPAIRS | | | SPECIFIED ON THE PERMIT APPLICATION. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- SPECIFY ROOF PITCH AS REQUIRED BY CITY POLICY FOR | | | RE-ROOFING PERMITS. | | | | | | 3- FLAT ROOF NOA 14-0529.02 SUBMITTED: | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 FBC-RESIDENTIAL, 5TH EDITION | | | (2014). | | | | | | B) IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES OF SEC. R301, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION #7 ON | | | LAST PAGE ON NOA SUBMITTED. | | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE | | | USED IF THE DESIGN PRESSURES SHOWN ON THE ASSEMBLY | | | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|