| 2016-09-13 17:21:18 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 285 CORDOVA RD |
| | DESCRIPTION: PLAN REVIEW COMMENTS & CORRECTIONS |
| | PERMIT # 16070009 |
| | |
| | BELOW PLEASE FIND MY RESPONSE TO THE SUBMITTED |
| | NARRATIVE IN CHRONOLOGICAL TO THE NARRATIVE. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. IF THIS IS A TWO PERMIT PROJECT WHY CLUTTER THE |
| | SUBMITTAL WITH INFORMATION NOT RELATED TO THIS |
| | PARTICULAR PERMIT UNLESS IT IS FOR REFERENCE ONLY AND |
| | IN SUCH CASE INDICATE SO. THIS WAY ONLY THE CORRECT |
| | SCOPE OF WORK IS APPROVED. |
| | 2. IF THE METER & MAIN ARE TO BE RELOCATED UNDER A |
| | SEPARATE PERMIT OR IN THE FUTURE, YOU SHALL INDICATE ON |
| | THE PLANS THE CURRENT LOCATION OF THESE ITEMS. |
| | OBVIOUSLY THIS WILL AFFECT THE SOURCE OF ELECTRICAL |
| | POWER TO THE LOCATION INDICATED FOR THE NEW PANEL. |
| | 3. THERE IS NOTHING WRONG WITH THE WAY THE PROPOSED |
| | SERVICE, BUT IF UNDER SEPARATE PERMIT, THAT PERMIT |
| | SHALL BE RUNNING SIMULTANEOUS TO THESE OTHERWISE THERE |
| | WILL BE PROBLEMS WITH THE ELECTRICAL PLAN REVIEW AND |
| | SUBSEQUENT INSPECTIONS. FURTHERMORE, SEE NOTES FOR |
| | ITEMS LACKING FROM THE RISER DIAGRAM AS SUBMITTED. |
| | 4. OK FOR THE PROPOSED SERVICE, BUT AS INDICATED ABOVE, |
| | UNLESS THE WORK IS BEING DONE SIMULTANEOUSLY, THE |
| | CURRENT CONDITIONS SHALL BE INDICATED ON THE DRAWINGS. |
| | IF THE PERMIT FOR THE SERVICE WORK IS TO ACCOMPANY |
| | THESE, A SITE DRAWING SHOWING THE LOCATION OF THE |
| | EXISTING SERVICE AND ELECTRICAL PANELS AND THE PROPOSED |
| | LOCATION IS REQUIRED. YOU ARE TO SHOW ON THE PLAN THE |
| | ROUTE OF THE SERVICE FEEDER AND INDICATE IF AERIAL OR |
| | UNDERGROUND. |
| | 5. OK. ADD A BLOCK NOTE TO THE PLANS INDICATING SO. |
| | 6. OK AS CORRECTED BUT PREFER TO HAVE IT SHOWN ON THE |
| | RISER. |
| | 7. OK AS CORRECTED. |
| | 8. OK AS CORRECTED. |
| | 9. OK AS CORRECTED. |
| | 10. OK AS CORRECTED. |
| | 11. SEE NOTE FOR PERMIT 16070007 FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |