2016-07-14 18:13:101ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
 PERMIT #: 16070009
 JOB NAME: JOHN HARTNER
 JOB ADDRESS: 285 CORDOVA RD., WEST PALM BEACH, FL
 DESCRIPTION: CONSTRUCTION OF AN ACCESSORY BLDG.
  
 1. BLDG. DEPARTMENT NOTES AS MENTIONED ON THE PLANS ARE
 REFERRING TO AN OUTDATED CODE. THE CODE IN EFFECT NOW
 IS THE 2011 EDITION OF THE NEC. PLEASE CORRECT YOUR
 NOTES ACCORDINGLY.
 2. PER NOTE ON APPROVED PLAN, THE NEW METER AND MAIN
 PANEL TO BE UNDER SEPARATE PERMIT.
 3. FBC-RE3601.2/NEC230.2: ONE AND TWO FAMILY DWELLINGS
 SHALL BE SERVED BY ONLY ONE SERVICE. THE PLANS AS
 SUBMITTED SHOW YOUR SERVICES SCATTERED THROUGHOUT THE
 PROPERTY IN VIOLATION OF THIS SECTION AS STATED IN THE
 NEXT COMMENT.
 4. FBC-RE3601.7/NEC 230.72 GROUPING OF DISCONNECTS. (A)
 GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN NEC
 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE
 MARKED TO INDICATE THE LOAD SERVED.
 5. IMPORTANT NOTICE: ALL TRENCHES SHALL REMAIN OPEN FOR
 INSPECTION UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR. NO SITE TUBES WILL BE ACCEPTED
 6. FBC-ER3609/ NEC 250.94 BONDING FOR OTHER SYSTEMS.
 THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 7. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS.
 BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON
 CEILING BOXES ON PAGE.
 8. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 9. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 10. FBC-R315: BECAUSE YOU ARE USING FOSSIL FUEL BURNING
 APPLIANCES YOU SHALL COMPLY WITH THE CARBON MONOXIDE
 DETECTOR REQUIREMENTS OF THIS CODE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  