| 2016-07-14 18:13:10 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | PERMIT #: 16070009 |
| | JOB NAME: JOHN HARTNER |
| | JOB ADDRESS: 285 CORDOVA RD., WEST PALM BEACH, FL |
| | DESCRIPTION: CONSTRUCTION OF AN ACCESSORY BLDG. |
| | |
| | 1. BLDG. DEPARTMENT NOTES AS MENTIONED ON THE PLANS ARE |
| | REFERRING TO AN OUTDATED CODE. THE CODE IN EFFECT NOW |
| | IS THE 2011 EDITION OF THE NEC. PLEASE CORRECT YOUR |
| | NOTES ACCORDINGLY. |
| | 2. PER NOTE ON APPROVED PLAN, THE NEW METER AND MAIN |
| | PANEL TO BE UNDER SEPARATE PERMIT. |
| | 3. FBC-RE3601.2/NEC230.2: ONE AND TWO FAMILY DWELLINGS |
| | SHALL BE SERVED BY ONLY ONE SERVICE. THE PLANS AS |
| | SUBMITTED SHOW YOUR SERVICES SCATTERED THROUGHOUT THE |
| | PROPERTY IN VIOLATION OF THIS SECTION AS STATED IN THE |
| | NEXT COMMENT. |
| | 4. FBC-RE3601.7/NEC 230.72 GROUPING OF DISCONNECTS. (A) |
| | GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN NEC |
| | 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE |
| | MARKED TO INDICATE THE LOAD SERVED. |
| | 5. IMPORTANT NOTICE: ALL TRENCHES SHALL REMAIN OPEN FOR |
| | INSPECTION UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| | ELECTRICAL INSPECTOR. NO SITE TUBES WILL BE ACCEPTED |
| | 6. FBC-ER3609/ NEC 250.94 BONDING FOR OTHER SYSTEMS. |
| | THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | 7. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS. |
| | BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| | CEILING BOXES ON PAGE. |
| | 8. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 9. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. |
| | 10. FBC-R315: BECAUSE YOU ARE USING FOSSIL FUEL BURNING |
| | APPLIANCES YOU SHALL COMPLY WITH THE CARBON MONOXIDE |
| | DETECTOR REQUIREMENTS OF THIS CODE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |