| 2016-09-13 16:39:05 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 285 CORDOVA RD |
| | DESCRIPTION: PLAN REVIEW COMMENTS & CORRECTIONS |
| | PERMIT # 16070007 |
| | |
| | THOUGH NOT INDICATED ON RESUBMITTAL FORM, THE NEW |
| | SUBMITTAL HAS NEW ELECTRICAL SHEETS AND THEREFORE HAD |
| | TO BE REVIEWED ALL OVER. BELOW PLEASE FIND A LIST OF |
| | REQUIRED CORRECTIONS. ADDITIONAL CORRECTIONS MAY BE |
| | REQUIRED AFTER REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH |
| | DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE |
| | GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS |
| | SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE. |
| | CORRECT NOTE 12 ON THE ELECTRICAL SHEET. |
| | 2. SHOW ON THE ELECTRICAL PLAN OR PROVIDE A SITE PLAN |
| | SHOWING THE LOCATION OF THE ELECTRIC UTILITY POLE |
| | SERVICE THE PROPERTY ALONG WITH THE LOCATION OF THE |
| | EXISTING METER AND MAIN DISCONNECT ALONG WITH THE NEW |
| | LOCATION. INDICATE ON THE DRAWING THE LOCATION OF THE |
| | SERVICE FEEDER WEATHER OVERHEAD OR UNDERGROUND. |
| | 3. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET |
| | LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT |
| | RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN |
| | ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| | ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, |
| | 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE ?WR?. CORRECT NOTE 10 & 16 |
| | ACCORDINGLY. |
| | 4. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| | SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| | SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| | SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| | SITE SPECIFIC. |
| | 5. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM |
| | LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT |
| | LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE |
| | E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| | DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| | FEEDERS IN ACCORDANCE WITH CHAPTER 37. |
| | 6. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS |
| | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL |
| | INSPECTOR. NO SITE TUBES WILL BE ACCEPTED THS VAN BE |
| | ADDRESSED WITH A BLOCK NOTE. |
| | 7. FBC-ER3901.12 NEC 210.63 HVAC EQUIPMENT SERVICE |
| | OUTLET. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE |
| | EQUIPMENT. THE PLANS DO SHOW THIS RECEPTACLE BUT IT |
| | APPEARS TO BE BEHIND THE CU IN VIOLATION OF NEC 110.26. |
| | CORRECT ACCORDINGLY. |
| | 8. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS. THIS TOO CAN BE ADDRESSED |
| | WITH A BLOCK NOTE. |
| | 9. FBC-RE3803.10/NEC 300.5(B) WET LOCATIONS: THE |
| | INTERIOR OF ENCLOSURES OR RACEWAYS INSTALLED |
| | UNDERGROUND SHALL BE CONSIDERED TO BE A WET LOCATION. |
| | INSULATED CONDUCTORS AND CABLES INSTALLED IN SUCH |
| | ENCLOSURES OR RACEWAYS IN UNDERGROUND INSTALLATIONS |
| | SHALL BE LISTED FOR USE IN WET LOCATIONS. CONNECTIONS |
| | OR SPLICES IN AN UNDERGROUND INSTALLATION SHALL BE |
| | APPROVED FOR WET LOCATIONS. INDICATE PROPOSED CONDUCTOR |
| | TYPES ON THE ELECTRICAL RISER DIAGRAM. |
| | 10. PLANS REFLECT TWO DIFFERENT AND CONFLICTING |
| | ELECTRICAL RISER DIAGRAMS. DELETE THE ONE NOT |
| | APPLICABLE TO THE PERMIT IN QUESTION AND CORRECT THE |
| | OTHER ACCORDING TO THE COMMENTS ABOVE. |
| | 11. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE |
| | A PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY |
| | INDICATING THE SPECIFIC PURPOSE OF EVERY CIRCUIT. |
| | PROVIDE A CIRCUIT DIRECTORY FOR EVERY PANEL BEING |
| | WORKED ON AND HAVE IT MATCH THE ELECTRICAL RISER |
| | DIAGRAM. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |