| Plan Review Notes For Permit 16070001 |
| Permit Number |
16070001 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-10 17:09:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) A MECHANICAL PERMIT IS REQUIRED TO RELOCATE THE A/C | | | CONDENSER. FBC 105.1 | | | | | | 2) SPECIFY THE EXISTING LOCATION OF THE A/C CONDENSER | | | PRIOR TO BEING LOCATED. FBC 107.2.1 | | | | | | 3) PROVIDE A DETAIL OF THE CONDENSER PAD WITH ANCHORING | | | DETAILS. FBCR M1401.4 AND M1305.1.4.1 |
|