| Date |
Text |
| 2016-08-17 13:01:14 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) SHEET E 1.1 - ONLY ONE (1) PHONE HEADSET IS |
| | INDICATED ON THE PLAN SHEET. THE AREA OF REFUGE |
| | COMMUINCATION SYSTEM SHALL BE PROVIDED AS REQUIRED BY |
| | NFPA 101, CHAPTER 7. |
| | |
| | 7.2.12 AREAS OF REFUGE. |
| | 7.2.12.1 GENERAL. |
| | 7.2.12.1.1 AN AREA OF REFUGE USED AS PART OF A REQUIRED |
| | ACCESSIBLE MEANS OF EGRESS IN ACCORDANCE WITH 7.5.4; |
| | CONSISTING OF A STORY IN A BUILDING THAT IS PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7; AND |
| | HAVING AN ACCESSIBLE STORY THAT IS ONE OR MORE STORIES |
| | ABOVE OR BELOW A STORY OF EXIT DISCHARGE SHALL MEET THE |
| | FOLLOWING CRITERIA: |
| | (1) EACH ELEVATOR LANDING SHALL BE PROVIDED WITH A |
| | TWO-WAY COMMUNICATION SYSTEM FOR COMMUNICATION BETWEEN |
| | THE ELEVATOR LANDING AND THE FIRE COMMAND CENTER OR A |
| | CENTRAL CONTROL POINT APPROVED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | (2) DIRECTIONS FOR THE USE OF THE TWO-WAY COMMUNICATION |
| | SYSTEM, INSTRUCTIONS FOR SUMMONING ASSISTANCE VIA THE |
| | TWO-WAY COMMUNICATION SYSTEM, AND WRITTEN |
| | IDENTIFICATION OF THE LOCATION SHALL BE POSTED ADJACENT |
| | TO THE TWO-WAY COMMUNICATION SYSTEM. |
| | (3) THE TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE BOTH |
| | AUDIBLEAND VISIBLE SIGNALS |
| | |
| | |
| | 7.2.12.2.5 THE AREA OF REFUGE SHALL BE PROVIDED WITH A |
| | TWO-WAY COMMUNICATION SYSTEM FOR COMMUNICATION BETWEEN |
| | THE AREA OF REFUGE AND A CENTRAL CONTROL POINT. THE |
| | DOOR OPENING TO THE STAIR ENCLOSURE OR THE ELEVATOR |
| | DOOR AND THE ASSOCIATED PORTION OF THE AREA OF REFUGE |
| | THAT THE STAIR ENCLOSURE DOOR OPENING OR ELEVATOR DOOR |
| | SERVES SHALL BE IDENTIFIED BY SIGNAGE. (SEE |
| | 7.2.12.3.5.) |
| | |
| | |
| | 7.2.12.2.6* INSTRUCTIONS FOR SUMMONING ASSISTANCE, VIA |
| | THE TWOWAY COMMUNICATION SYSTEM, AND WRITTEN |
| | IDENTIFICATION OF THE AREA OF REFUGE LOCATION SHALL BE |
| | POSTED ADJACENT TO THE TWO-WAY COMMUNICATION SYSTEM. |
| | |
| | |
| | AS PER DISCUSSION WITH GLENN PATE, ARCHITECT, PROVIDE A |
| | 2ND PHONE HEADSET IN THE FRONT OF THE BUILDING LOCATED |
| | IN AN AREA COORDINATED WITH THE FIRE MARSHAL'S OFFICE |
| | AND PROVIDE A REVISION. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |