| 2016-08-11 15:31:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16061686 |
| | ADD: 415 NORTHWOOD RD. |
| | CONT: INGECO CONTRACTORS LLC |
| | TEL: 561-601-2379 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. AUGUST 22/ 2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | AREA OF REFUGE DOCUMENTS AND LULA LIFT DOCUMENTS WILL |
| | BE REQUIRED TO BE REVIEWED AND APPROVED BY PLAN REVIEW |
| | BEFORE THE FRAMING INSPECTION CAN OCCUR!!! |
| | |
| | 1) AREA OF REFUGE SHALL COMPLY WITH THESE REQUIREMENTS. |
| | AREA OF REFUGE. 2003 IBC-B 1007.6 .3 TWO-WAY |
| | COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH |
| | TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE |
| | AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS |
| | NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO |
| | HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM. |
| | LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED |
| | BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM |
| | SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS. |
| | |
| | 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE A |
| | TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS |
| | ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL |
| | BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE |
| | INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING; |
| | 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS. |
| | 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON |
| | AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS. |
| | 3) INFORMATION ON THE PLANNED AVAILABILITY OF |
| | ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION |
| | OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4) |
| | DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS |
| | SYSTEM. |
| | |
| | 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS TO |
| | AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL BE |
| | IDENTIFIED BY A SIGN COMPLYING WITH ICC A117., STATING |
| | AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL SYMBOL |
| | OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION IS |
| | REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN |
| | SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE |
| | COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR |
| | TO AN AREA OF REFUGE. |
| | |
| | 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A |
| | REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED |
| | ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED |
| | INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS. |
| | |
| | 2) SHOP DRAWINGS WILL BE REQUIRED FOR THE LULA LIFT |
| | (LIMITED-USE / LIMITED-APPLICATION ELEVATORS) THAT WILL |
| | SHOW COMPLIANCE WITH 2014 FBC-ACCESS |
| | 408.1L. LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL |
| | COMPLY WITH 408 AND WITH ASME A17.1. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | CODE 408.1- 408.4.8 & ASME A17.1 |