| Plan Review Notes For Permit 16061686 |
| Permit Number |
16061686 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-28 06:56:14 | 1) SHT. LS-1 - THE BUILDING CODE DATA LISTS A BUSINESS | | | OCCUPANCY BUT A BUSINESS AREA IS NOT SHOWN ON THE | | | PLANS. CLARIFY. | | | 2) SEPARATE FACILITIES SHALL BE PROVIDED FOR THE MALES | | | AND FEMALES. 2014 FBC-PLUMBING SEC. 403.1.1, 403.2. | | | BOTH TOILET ROOMS SHALL BE HANDICAPPED ACCESSIBLE PER | | | THE 2014 FBC-ACCESS. SEC.213.2. | | | 3) VERTICAL ACCESSIBILITY SHALL BE PROVIDED FOR THE | | | TOILET ROOM ON THE SECOND FLOOR.FBC-ACCESSIBILITY SEC. | | | 201.1.1. | | | 4) THE DRINKING FOUNTAINS SHALL COMPLY WITH FBC-ACCESS. | | | SECS.204.1 7 307 FOR PROTRUDING OBJECTS. | | | 5) THE FINISH SCHEDULE ON SHT. A-1 SHOWS THE WALLS IN | | | THE TOILET ROOMS AND JANITORS CLOSET TO BE PAINT.WALLS | | | AND PARTITIONS WITHIN TWO FEET OF SERVICE SINKS, | | | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | | NONABSORBANT SURFACE TO A HEIGHT OF NO LESS THAN FOUR | | | FEET ABOVE THE FLOOR PER 2014 FBC SEC.1210.2.2. | | | 6) THE PLAN SHOWS PRODUCTION AREAS. SUBMIT INFORMATION | | | AS TO WHAT TYPE OF PROCESSES WILL BE PERFORMED IN THESE | | | AREAS. WPB AMEND. TO 2014 FBC SEC.107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|