Plan Review Notes
Plan Review Notes For Permit 16061686
Permit Number 16061686
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-11 12:05:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061686
 7/11/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) M4.1: AC 2-1 IS MISLABELED AS A 5-TON SYSTEM.
  
 3) M4.1: THE VENTILATION CALCULATIONS DO NOT INCLUDE A
 BREAKDOWN FOR THE PRODUCTION 101 AREA OF THE PROPOSED
 OCCUPANCY. PLEASE CLARIFY WHAT TYPE OF WORK WILL BE
 PERFORMED THERE AND WHAT TYPE OF EQUIPMENT WILL BE
 USED.
  
 3) EF-1-1 AND 2-1 SHALL EACH HAVE MINIMUM 70 CFM
 CAPACITIES- TABLE 403.3.
  
 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS- SECTION 307. NOTE: NO DETAILS ARE SHOWN ON
 THE PLUMBING PLANS.
  
 4) SUBMIT COPIES OF THE FL. PRODUCT APPROVAL FOR THE AC
 STAND, AND THE MIAMI-DADE NOA FOR THE O/A LOUVER WITH
 SHOP DRAWING SIGNATURES BY THE EOR.
  