| Plan Review Notes For Permit 16061686 |
| Permit Number |
16061686 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-11 12:05:44 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16061686 | | | 7/11/16 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) M4.1: AC 2-1 IS MISLABELED AS A 5-TON SYSTEM. | | | | | | 3) M4.1: THE VENTILATION CALCULATIONS DO NOT INCLUDE A | | | BREAKDOWN FOR THE PRODUCTION 101 AREA OF THE PROPOSED | | | OCCUPANCY. PLEASE CLARIFY WHAT TYPE OF WORK WILL BE | | | PERFORMED THERE AND WHAT TYPE OF EQUIPMENT WILL BE | | | USED. | | | | | | 3) EF-1-1 AND 2-1 SHALL EACH HAVE MINIMUM 70 CFM | | | CAPACITIES- TABLE 403.3. | | | | | | 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR | | | HANDLERS- SECTION 307. NOTE: NO DETAILS ARE SHOWN ON | | | THE PLUMBING PLANS. | | | | | | 4) SUBMIT COPIES OF THE FL. PRODUCT APPROVAL FOR THE AC | | | STAND, AND THE MIAMI-DADE NOA FOR THE O/A LOUVER WITH | | | SHOP DRAWING SIGNATURES BY THE EOR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|