Notes
Date Text
2016-07-15 07:34:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 3. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY UTILITY FOR APPROVAL. NEC 110.24 FBC 107
 4. CHANGES ARE SHOWN TO THE EXISTING SERVICE
 ARRANGEMENTS. LABEL MAINS TO INDICATE MAIN 1 OF 3 AND 2
 OF 3 ETC, ALSO COMPLY WITH THE REQUIRED SIGNAGE TO
 ASSIST FIRST RESPONDERS. NEC 230.70B
 5. LABEL ALL MAINS TO RATED FOR SERVICE ENTRANCE. SHOW
 METER AMP RATINGS.
 6. PROVIDE A NOTE PER PLAN TO USE EXISTING BOX AS A
 JUNCTION BOX, THAT EQUIPMENT IS TO BE LISTED AND
 LABELED PER NEC 110.3B
 7. SHEET E1.1 SHOW ROOFTOP RECEPTACLES TO WP/ GFCI
 PROTECTED NEC 210.8B
 8. LABEL FOUNTAIN RECEPTACLES TO BE GFCI PROTECTED PER
 NEC 422.52
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  