| Plan Review Notes For Permit 16061671 |
| Permit Number |
16061671 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-07 13:54:37 | 1807 DIVISION AVENUE | | | PERMIT #16061671 | | | MASTER #15050261 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | | CONNECTION. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION AND THE ADDRESS OF THE BUILDING | | | BEING SERVED. | | | | | | SHEET FP-203: PROVIDE A DWELLING UNIT HYDRAULIC | | | CALCULATION SUPPORTING THE USE OF 4 SPRINKLERS ON | | | 1-1/2" BRANCH LINE. | | | | | | SHEET FP-205: SECTION BB DETAIL STATES THE SIDEWALL | | | MODEL VK460 K-5.8 IS TO BE LOCATED 6" BELOW THE | | | CEILING; HOWEVER, THE ACTUAL PIPE DROP DETAIL APPEARS | | | TO SHOW A 12" DROP. WHICH VALUE IS THE CORRECT VALUE? | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|