Date Text
2016-07-07 13:54:371807 DIVISION AVENUE
 PERMIT #16061671
 MASTER #15050261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION AND THE ADDRESS OF THE BUILDING
 BEING SERVED.
  
 SHEET FP-203: PROVIDE A DWELLING UNIT HYDRAULIC
 CALCULATION SUPPORTING THE USE OF 4 SPRINKLERS ON
 1-1/2" BRANCH LINE.
  
 SHEET FP-205: SECTION BB DETAIL STATES THE SIDEWALL
 MODEL VK460 K-5.8 IS TO BE LOCATED 6" BELOW THE
 CEILING; HOWEVER, THE ACTUAL PIPE DROP DETAIL APPEARS
 TO SHOW A 12" DROP. WHICH VALUE IS THE CORRECT VALUE?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]