| Notes |
| Date |
Text |
| 2016-08-09 07:20:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. I WAS UNABLE TO LOCATE WIND DESIGN CRITERIA ON THIS | | | PLAN, FBC 1609. THE MASTER FOR THIS REVISION | | | (16010527), SHEET S213, HAS A NOTE REGARDING COMPONENTS | | | & CLADDING WIND PRESSURE 169MPH ULTIMATE. AS THE SCOPE | | | OF THIS PERMIT INCLUDES THE TRELLIS, GATES, AND WALL, | | | PLEASE CLARIFY WIND DESIGN CRITERIA (WIND SPEED, | | | EXPOSURE). | | | | | | 2. PEDERSTRIAN GATES ARE DEPICTED ON THE ARCH SHEETS. | | | ALL GATES IN THE MEANS OF EGRESS (EXIT DISCHARGE) FOR | | | THE ASSEMBLY OCCUPANCY ARE TO INCLUDE PANIC DEVICES OR | | | FIRE EXIT HARDWARE, FBC 1008. | | | | | | |
|