Plan Review Notes
Plan Review Notes For Permit 16061663
Permit Number 16061663
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-09 07:20:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. I WAS UNABLE TO LOCATE WIND DESIGN CRITERIA ON THIS
 PLAN, FBC 1609. THE MASTER FOR THIS REVISION
 (16010527), SHEET S213, HAS A NOTE REGARDING COMPONENTS
 & CLADDING WIND PRESSURE 169MPH ULTIMATE. AS THE SCOPE
 OF THIS PERMIT INCLUDES THE TRELLIS, GATES, AND WALL,
 PLEASE CLARIFY WIND DESIGN CRITERIA (WIND SPEED,
 EXPOSURE).
  
 2. PEDERSTRIAN GATES ARE DEPICTED ON THE ARCH SHEETS.
 ALL GATES IN THE MEANS OF EGRESS (EXIT DISCHARGE) FOR
 THE ASSEMBLY OCCUPANCY ARE TO INCLUDE PANIC DEVICES OR
 FIRE EXIT HARDWARE, FBC 1008.
  
  