| Plan Review Notes For Permit 16061662 |
| Permit Number |
16061662 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-01 14:39:22 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16061662 | | | 7/1/16 | | | | | | 1) PLEASE PLACE REVISION CLOUDS AND A DELTA TRIANGLE ON | | | THE PLAN INDICATING THE LOCATIONS OF REVISION 2. | | | | | | 2) PROVIDE RETURN AIR FROM THE OFFICES- SECTION 601.5 | | | | | | 3) INDICATE THE CFM CAPACITIES OF THE DIFFUSERS IN THE | | | OFFICES THAT ARE SHOWN AT THE TOP LEFT CORNER OF THE | | | PLAN SHEET. | | | | | | 4) INCLUDE THE LINEAR DIFFUSERS IN THE DEVICE SHCEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | 2016-07-01 12:49:54 | CCOLE |
|