| Plan Review Notes For Permit 16061642 |
| Permit Number |
16061642 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-30 19:01:34 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - APPLICATION STATES THAT THE HOUSE WILL BE RE-WIRED | | | BECAUSE OF THE OLD STYLE KNOB & TUBE WIRING NO FLOOR | | | PLAN SUBMITTED. FBC 107 INSUFFICIENT DOCUMENTS | | | | | | - ELECTRICAL PLANS TO INCLUDE FBC RESIDENTIAL | | | | | | 1) E3902.6 KITCHEN RECEPTACLES GFCI, E3902.12 ARC-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION | | | | | | 2) E3903.2 HABITABLE ROOM LIGHTING, E4002.14 | | | TAMPER-RESISTANT RECEPTACLES | | | | | | 3) SMOKE ALARMS PER SECTIONS 314 AND 315. | | | | | | | | | | | | |
|