| Plan Review Notes For Permit 16061598 |
| Permit Number |
16061598 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-13 18:27:29 | I HAD THIS FILE ON MY DESK WAITING TO HEAR BACK FROM | | | THE EC. BY 7/13/16 I HAD NOT HEARD FROM HIM SO I ROUTED | | | TO SMALL DENIED DRAWER A. MA | | 2016-06-29 16:00:21 | I PLACED A CALL TO THE EC TO INQUIRE ON THE LOCATION OF | | | THE SERVICE DISCONNECTS TO ASCERTAIN COMPLIANCE W/NEC | | | 230.70(A)(1). THE DRAWING IS ALSO LACKING THE | | | INTER-SYSTEM BONDING TERMINAL REQUIRED IN NEC 250.94. |
|