| Plan Review Notes For Permit 16061554 |
| Permit Number |
16061554 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-30 14:04:23 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR THE FLAT ROOF COATING SPECIFIED | | | ON THE "ESTIMATE CONTRACT" SUBMITTED. | | | NOTE: NEED PRODUCT APPROVAL TO REVIEW THE REQUIREMENTS | | | FOR PROPER USE AND LIMITATIONS. | | | | | | 2- "ESTIMATE CONTRACT" SUBMITTED SPECIFIES "RAFTERS TO | | | BE REPAIRED AS TYPE OF CONSTRUCTION WILL ALLOW". | | | ROOFING CONTRACTOR CAN NOT DO THIS WORK UNLESS | | | CONTRACTOR IS LICENSED TO DO THIS TYPE OF STRUCTURAL | | | WORK. IF ROOFING CONTRACTOR IS NOT LICENSED TO DO | | | STRUCTURAL WORK, THEN WORK NEEDS TO BE SUB-CONTRACTED | | | TO CONTRACTOR THAT IS LICENSED TO DO THE WORK. | | | SUB-PERMIT IS REQUIRED FOR THIS CAN OF WORK ALONG WITH | | | COMPLETE DETAILS AND SPECIFICATIONS FOR THE STRUCTURAL | | | REPAIR. SEC. 489.113 F.S. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|