| Plan Review Notes For Permit 16061550 |
| Permit Number |
16061550 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-06 16:15:45 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - NEC 406.12 TAMPER-RESISTANT RECEPTACLES IN DWELLING | | | UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, | | | 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER | | | RESISTANT RECEPTACLES. | | | | | | - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE | | | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY | | | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 | | | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE | | | DISTANCE FROM THE EDGE OF THE WALL. | | | | | | - NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | | | | - NEC 210.70(1) A LIGHTING OUTLET IS REQUIRED IN EVERY | | | HABITABLE ROOM TO BE CONTROLLED BY AT LEAST 1 WALL | | | SWITCH. | | | |
|