Plan Review Notes
Plan Review Notes For Permit 16061546
Permit Number 16061546
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-29 15:11:231ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. NEC 215.5: IN ADDITION TO THE RISER DIAGRAM
 SUBMITTED YOU SHALL SUBMIT LOAD CALCS AND A PANEL
 SCHEDULE.
 2. NEC 250.9: AN INTER-SYSTEM BONDING TERMINAL IS
 REQUIRED AT THE SERVICE.
 3. NEC 625 PART V: THERE ARE SPECIFIC REQUIREMENTS
 ACCORDING TO THE LOCATION OF THE CHARGERS. YOUR DRAWING
 DOES NOT REFLECT THE LOCATION OF THE CHARGERS THEREFORE
 THE REQUIREMENTS FOR SUCH ARE UNDETERMINED. PROVIDE A
 DOCUMENT INDICATING THE LOCATION OF EACH CHARGER ALONG
 WITH THE WIRING TO EACH.
 4. EXPLAIN WHAT IS BEING DONE TO RELOCATE FPL FEEDER
 CONDUIT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  