 PLUMBING COMMENTS:
  
 1. THE TUB OVER FLOW SHALL BE ON THE TUB SIDE OF THE
 P-TRAP IF INSTALLED AS SHOWN IT WOULD NOT BE TRAPPED
 AND WOULD ALLOW SEWER GAS INTO BATHROOM. PER WPB AMEND
 TO FBC 107.2.1
  
 3.THE WASHING MACHINE STACK SHALL CONNECT DOWN STREAM
 OF BATHROOM GROUP IT'S NOT ALLOWED TO CONNECT TO THE
 HORIZONTAL WET VENT. PER FBC PL P3108.1
  
 4. PROVIDE NOT ON PLAN A) SHUT OFF VALVES FOR WASHING
 MACHINE SHALL BE ACCESSIBLE B) SLIP JOINTS ON TUB DRAIN
 SHALL BE ACCESSIBLE C) THE TUB AND SHOWER VALVE SHALL
 COMPLY WITH FBC RES P2708.3
 PER WPB AMEND TO FBC 107.2.1
  
 5. EXHAUST FOR THE BATHROOM SHALL COMPLY WITH FBC RES
 R303.3 OR FBC RES M1507 IT IS NOT CLEARLY SHOWN ON PLAN
 IF USING MECHANICAL VENT PROVIDE CFM.
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  