| Plan Review Notes For Permit 16061486 |
| Permit Number |
16061486 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-04-07 15:00:20 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE TUB OVER FLOW SHALL BE ON THE TUB SIDE OF THE | | | P-TRAP IF INSTALLED AS SHOWN IT WOULD NOT BE TRAPPED | | | AND WOULD ALLOW SEWER GAS INTO BATHROOM. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 3.THE WASHING MACHINE STACK SHALL CONNECT DOWN STREAM | | | OF BATHROOM GROUP IT'S NOT ALLOWED TO CONNECT TO THE | | | HORIZONTAL WET VENT. PER FBC PL P3108.1 | | | | | | 4. PROVIDE NOT ON PLAN A) SHUT OFF VALVES FOR WASHING | | | MACHINE SHALL BE ACCESSIBLE B) SLIP JOINTS ON TUB DRAIN | | | SHALL BE ACCESSIBLE C) THE TUB AND SHOWER VALVE SHALL | | | COMPLY WITH FBC RES P2708.3 | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. EXHAUST FOR THE BATHROOM SHALL COMPLY WITH FBC RES | | | R303.3 OR FBC RES M1507 IT IS NOT CLEARLY SHOWN ON PLAN | | | IF USING MECHANICAL VENT PROVIDE CFM. | | | | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|