| Plan Review Notes For Permit 16061486 |
| Permit Number |
16061486 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-23 10:41:42 | 1) SUBMIT A SANITARY RISER THAT COMPLIES WITH THE 2014 | | | FBCR-PLUMBING. THERE ARE TOO MANY VIOLATIONS TO LIST. | | | 2) TUB VALVE SHALL COMPLY WITH 2014 FBCR SEC. P2708.3. | | | 3) IF SLIP CONNECTIONS ARE USED ON THE TUB, COMPLY WITH | | | 2014 FBCR SEC. P 2704. | | | 4) LOCATION OF PLUMBING FIXTURES SHALL COMPLY WITH 2014 | | | FBCR SEC.P2705. | | | 5) THE SLOPE OF THE DRAINAGE PIPE SHALL COMPLY WITH | | | 2014 FBCR SEC.P3002.3.1. | | | 6) WATER SUPPLY VALVES FOR THE WASHER/DRYER STACKED | | | UNIT SHALL COMPLY WITH 2014 FBCR SEC.P2903.9.3. | | | 7) AIR ADMITTANCE VALVES SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND 2014 FBCR SEC.P3114. | | | 8) SIZING OF VENTS SHALL COMPLY WITH 2014 FBCR | | | SEC.P3113.1. | | | 9) THE DRAIN & TRAP SIZE FOR THE WASHING MACHINE SHALL | | | COMPLY WITH 2014 FBCR SEC. P3201.7. | | | 10) CLEANOUTS ARE REQUIRED IN STACKS PER 2014 FBCR | | | SEC.P3005.2.6. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|