Plan Review Notes
Plan Review Notes For Permit 16061486
Permit Number 16061486
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-23 10:41:421) SUBMIT A SANITARY RISER THAT COMPLIES WITH THE 2014
 FBCR-PLUMBING. THERE ARE TOO MANY VIOLATIONS TO LIST.
 2) TUB VALVE SHALL COMPLY WITH 2014 FBCR SEC. P2708.3.
 3) IF SLIP CONNECTIONS ARE USED ON THE TUB, COMPLY WITH
 2014 FBCR SEC. P 2704.
 4) LOCATION OF PLUMBING FIXTURES SHALL COMPLY WITH 2014
 FBCR SEC.P2705.
 5) THE SLOPE OF THE DRAINAGE PIPE SHALL COMPLY WITH
 2014 FBCR SEC.P3002.3.1.
 6) WATER SUPPLY VALVES FOR THE WASHER/DRYER STACKED
 UNIT SHALL COMPLY WITH 2014 FBCR SEC.P2903.9.3.
 7) AIR ADMITTANCE VALVES SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND 2014 FBCR SEC.P3114.
 8) SIZING OF VENTS SHALL COMPLY WITH 2014 FBCR
 SEC.P3113.1.
 9) THE DRAIN & TRAP SIZE FOR THE WASHING MACHINE SHALL
 COMPLY WITH 2014 FBCR SEC. P3201.7.
 10) CLEANOUTS ARE REQUIRED IN STACKS PER 2014 FBCR
 SEC.P3005.2.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR