Plan Review Notes
Plan Review Notes For Permit 16061477
Permit Number 16061477
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-06 11:32:40BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/6/16
  
 1. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE PURPOSE OF THE STRUCTURAL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE PERMITTED DOCUMENTS.
 2. THE SPECIAL INSPECTOR SHALL SUBMIT (IN TRIPLICATE)
 TO THE ENFORCEMENT AGENCY A COMPLETED RESIDENT
 INSPECTOR FORM.
 3. THE SPECIAL INSPECTOR SHALL SUBMIT TO THE
 ENFORCEMENT AGENCY A RESUME' OF EXPERIENCE ON PREVIOUS
 PROJECTS. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW MAY BE SCHEDULED.
 4. THE CONTRACTOR SHALL SUBMIT TO THE ENFORCEMENT
 AGENCY A JOB SUMMARY OR HISTORY FOR THIS TYPE OF
 CONSTRUCTION.
 5. THE SPECIAL INSPECTOR, UPON COMPLETION OF THE
 BUILDING AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY, FILE A SIGNED AND SEALED STATEMENT WITH THE
 ENFORCEMENT AGENCY IN SUBSTANTIALLY THE FOLLOWING FORM:
 TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE ABOVE
 DESCRIBED CONSTRUCTION OF ALL STRUCTURAL LOAD BEARING
 COMPONENTS COMPLIES WITH THE PERMITTED DOCUMENTS AND
 THE SHORING AND RE-SHORING CONFORMS THE THE SHORING AND
 RE-SHORING PLANS SUBMITTED TO THE ENFORCEMENT AGENCY.
 6. ANY PROPOSAL TO INSTALL AN ALTERNATE STRUCTURAL
 PRODUCT OR SYSTEM TO WHICH BUILDING CODES APPLY SHALL
 BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR REVIEW FOR
 COMPLIANCE WITH THE CODES AND MADE PART OF THE
 ENFORCEMENT AGENCY'S RECORDED SET OF PERMIT DOCUMENTS.
 ALL SHORING AND RE-SHORING PROCEDURES, PLANS AND
 DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY
 FOR RECOREDKEEPING. EACH SHORING AND RE-SHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 7. ALL RHINOPLASTIC CONCRETE ADD-MIXTURES SHALL BE
 REVIEWED BY THE ENGINEER OF RECORD.
 8. FBC 3309.1 - WHERE REQUIRED. ALL STRUCTURES UNDER
 CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE
 PROVIDED WITH NO FEWER THAN ONE APPROVED PORTABLE FIRE
 EXTINGUISHER IN ACCORDANCE WITH SECTION 906 AND SIZED
 FOR NOT LESS THAN ORDINARY HAZARDS:
 9. FBC 3310.2 - WHERE REQUIRED. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND
 ADDITIONS TO ANY BUILDING.
 10. NOTICE ONLY - FOR PROJECTS EXCEEDING 6 MONTHS.
 PLEASE CALL THE CITY OF WEST PALM BEACH AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE. WITHOUT
 THIS, THE PERMIT SHALL EXPIRE AT 6 MONTHS RESULTING IN
 ABANDONMENT OF JOB DUE TO NO INSPECTION ACTIVITY.
  