| Plan Review Notes For Permit 16061471 |
| Permit Number |
16061471 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-29 11:18:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO INDICATIONS OR CLOUDS SHOWING THE AREAS | | | OF AS-BUILT OR REVISION. | | | | | | PER NFPA 1, CHAPTER 1 OF THE FLORIDA FIRE PREVENTION | | | CODE, 5TH EDITION: | | | | | | CHAPTER 1 ADMINISTRATION | | | | | | 1.14 PLAN REVIEW. | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | PLEASE PROVIDE FOR COMPLIANCE WITH THE ABOVE WITH | | | CLOUDS, NOTES, OR A LETTER SPECIFICALY INDICATING EACH | | | CHANGE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|