Plan Review Notes
Plan Review Notes For Permit 16061459
Permit Number 16061459
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-29 09:53:32REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE A NUETRAL LOAD CALCULATION IN ACCORDANCE TO
 NEC 220.61(A)(B)(C) TO VERIFY REDUCTION IN FEEDER WIRE
 SIZE.
  
 - KEEP IN MIND ELECTRICAL CONNECTION WITH DISSIMILIAR
 METALS SUCH AS ALUMINUM AND COPPER SHALL BE IDENTIFIED
 AND SUITABLE FOR THE USE PER NEC 110.14