| Date |
Text |
| 2016-06-29 09:53:32 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PROVIDE A NUETRAL LOAD CALCULATION IN ACCORDANCE TO | | | NEC 220.61(A)(B)(C) TO VERIFY REDUCTION IN FEEDER WIRE | | | SIZE. | | | | | | - KEEP IN MIND ELECTRICAL CONNECTION WITH DISSIMILIAR | | | METALS SUCH AS ALUMINUM AND COPPER SHALL BE IDENTIFIED | | | AND SUITABLE FOR THE USE PER NEC 110.14 |
|