| Plan Review Notes For Permit 16061443 |
| Permit Number |
16061443 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2017-08-02 14:33:28 | 1) THE TRENCH DRAIN DETAIL DOES NOT SHOW THAT THIS | | | DRAIN IS EQUIPPED WITH A WATER SEAL TRAP. COMPLY WITH | | | 2014 FBC-PLUMBING SEC. 1002.1. | | | 2) SUBMIT COMPLETE SPECIFICATIONS / DETAILS FOR THE PCU | | | UNIT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT.P5.06 - THE SAMPLING PORT THAT SHOWS THE DOUBLE | | | SANITARY TEE WITH A CAP AT THE BOTTOM IS NOT AN | | | ACCEPTED DESIGN BY THE CITY. THE TWO WAY CLEANOUT ON | | | THE DISCHARGE SIDE OF THE GREASE INTERCEPTOR CAN BE | | | USED AS THE SAMPLING PORT AS LONG AS IT IS A MINIMUM OF | | | 4 INCHES IN DIAMETER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|