| 2017-08-11 11:38:09 | 1) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR | | | CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS | | | CODE SEC.304.6.2.THIS SECTION REFERS TO ONE PERMANENT | | | OPENING FOR COMBUSTION AIR YET THE PLAN REFERS TO TWO | | | OPENINGS. CLARIFY. | | | 2) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR | | | CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS | | | CODE SEC.304.6.2.THIS SECTION REQIURES THE COMBUSTION | | | AIR OPENING TO HAVE 1 SQUARE INCH PER 3,000 BTU'S YET | | | THE PLAN NOTES THE TOTAL BTU LOAD BEING DIVIDED BY | | | 4,000. CLARIFY. | | | 3) PLEASE CLARIFY HOW THE 1058 FREE SQ. INCH AREA WAS | | | DETERMINED. SEC. 304.10 OF THE 2014 FGC NOTES THAT | | | METAL LOUVERSAND GRILLES WILL BE ASSUMED TO HAVE A 75 | | | PERCENT FREE AREA. THE DIMENSION OF THE LOUVERS ARE | | | SHOWN AS 54 X 36= 1944 X.75 = 1458 SQ. INCHES PER | | | LOUVER. CLARIFY. | | | 4) SPECIFICATIONS HAVE BEEN SUBMITTED FOR GAS SUPPLIED | | | MID-RANGE IRONERS BUT THIS EQUIPMENT IS NOT SHOWN ON | | | THE GAS RISER AND THE BTU LOAD IS NOT INCLUDED IN THE | | | TOTAL. CLARIFY.SUBMIT COMBUSTION AIR CALCULATIONS FOR | | | THIS PIECE OF EQUIPMENT. | | | 5) SHT. M2.02 - LAUNDRY APPLIANCE CALCULATIONS REFER TO | | | SF-2.1 TWICE. CLARIFY.THE PLAN ALSO NOTES THAT THEY ARE | | | THE MAKEUP AIR FANS FOR DBF 2.2 & 2.3. THE FAN SCHEDULE | | | ON SHT. M6.01 NOTES THESE UNITS AS "NOT USED." CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|