| 2017-03-20 06:32:40 | 1) SHT. A7.41 - INDICATE ON THE PLANS THAT THE SHOWER |
| | SEAT IN ALTERNATE ROLL-IN SHOWER IS OF THE FOLDING |
| | TYPE. 2014 FBC-ACCESSIBILITY SEC.610.3. 2ND REQUEST. |
| | 2) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING |
| | MACHINES PER 2014 FBC-PLUMBING SEC.1003.6. SUBMIT A |
| | DETAIL AND SIZING CALCULATIONS FOR THE UNIT. THE |
| | SUBMITTED RESPONSE NARRATIVE REFERS TO A DETAIL ON SHT. |
| | P5.01 BUT THERE IS NO DETAIL ON THIS PLAN AND I COULD |
| | NOT FIND A DETAIL ANYWHERE IN THE PLANS. 2ND REQUEST. |
| | 3) SHT. P4.03 - SANITARY RISER # S/14 - 13TH FLOOR |
| | TOILET ROOM #1305 BY STAIR # 2 - THE SANITARY RISER |
| | DOEES NOT COMPLY WITH FBC 2014-PLUMBING SECS. 912 OR |
| | 914 FOR A HORIZONTAL WET VET OR A CIRCUIT VENT. PLACING |
| | A VENT ON THE FIRST WATER CLOSET CONNECTED TO THE |
| | HORIZONTAL DRAIN WILLL CORRECT THIS ISSUE. 2ND REQUEST. |
| | 4) SHT. P4.03 - SANITARY RISER S/14 - 7TH FLOOR KING |
| | SUITE AND FLOORS 8 - 11 - A MAXIMUM OF 4 FIXTURE UNITS |
| | ARE PERMITTED ON A 2 INCH WET VENT PER 2014 |
| | FBC-PLUMBING SEC.912.3 & TABLE 912.3. THE RISER SHOWS 6 |
| | FIXTURE UNITS ON A WET VENT. |
| | 5) SHTS. P4.04 & P4.05 - WATER RISERS -WATER FILTERS, |
| | BEVERAGE DISPENSERS, COFFEE MACHINES AND NONCARBONATED |
| | BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW |
| | PERR 2014 FBC-PLUMBING SECS.608.16.1 & 608.16.10. THESE |
| | APPLIANCES ARE USUALLY UNDER CONTINUOUS PRESSURE AND A |
| | ATMOSPHERIC VACUUM BREAKER AS CALLED OUT ON THE PLANS |
| | DOES NOT MEET COMPLIANCE WITH THE NOTED CODE SECTIONS. |
| | NONCARBONATED & CARBONATED BEVERAGE DISPENSERS, COFFEE |
| | MACHINES, ETC. SHALL BE PROTECTED AGAINST BACKFLOW BY A |
| | BACKFLOW PREVENTER CONFORMING TO ASSE 1022. |
| | 6) SHT. P2.01 - # 25 SHOWS A 2 INCH DRAIN FROM A |
| | "SCRUBBER" TO THE GREASE WASTE AND SHT. P4.01 SHOWS A 1 |
| | INCH DRAIN FROM THE "SCRUBBER"". CLARIFY. SUBMIT |
| | DETAILS / INFORMATION FOR THE SCRUBBER. |
| | 7) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. 2014 FBC - PLUMBING SEC.1003.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |