| 2016-12-21 10:45:20 | 1) SHT.A7.41 - THE ACCESSIBLE SHOWERS APPEAR TO BE OF |
| | THE ALTERNATE ROLL-IN TYPE.THE SEATS LOCATED IN THE |
| | HANDICAPPED ACCESSIBLE SHOWERS SHALL COMPLY WITH 2014 |
| | FBC-ACCESS. SECS.610.3. THE SEAT SHALL EXTEND FROM THE |
| | ADJACENT SIDE WALL TO A POINT WITHIN 3 INCHES OF THE |
| | COMPARTMENT ENTRY. CLEARLY THE TYPE OF ROLL-IN SHOWER |
| | ON THE PLAN, STANDARD ROLL-IN TYPE OR ALTERNATE ROLL-IN |
| | TYPE. |
| | 2) SHT.A7.41 - THE TOILET PAPER DISPENSERS SHALL COMPLY |
| | WITH 2014 FBC-ACCESS. SEC.604.9.6 ( 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER). 2ND |
| | REQUEST. |
| | 3) SHT.A7.41 - DETAIL #13 - THE SHOWER SEAT GRAB BAR |
| | ADJACENT TO THE SEAT SHALL BE A MAXIMUM OF 6 INCHES |
| | FROM THE BACK WALL PER 2014 FBC-ACCESS. SEC.608.3.3. |
| | 3) A LINT INTERCEPTOR IS REQUIRED PER 2014 FBC-PLUMBING |
| | SEC.1003.6.SUBMIT A DETAIL AND SIZING CALCULATIONS.SEC |
| | 1003.2. A SCREEN PLACED IN A TROUGH/TRENCH DRAIN DOES |
| | NOT MEET THE INTENT. |
| | 4) SHT.P2.09 - STAIR # 1 - THERE IS A KEY NOTE #12 NEXT |
| | TO THE 4 INCH SANITARY LINE DOWN BUT THERE IS NO |
| | KEYNOTE #12 LISTED. CLARIFY. |
| | 5) SHT. P4.02 - KEYNOTE #1 IS SHOWN AS A 2 INCH VENT AT |
| | POINT "S" AND ALSO AS A 3 INCH VENT AT POINT |
| | "B".CLARIFY. IS IT 2 INCH OR 3 INCH? |
| | 6) SHT. P4.02 - THE URINAL IN THE MEN'S RESTROOM IS |
| | INSTALLED ON A VERTICAL WET VENT WHICH IS NOT PERMITTED |
| | PER 2014 FBC-PLUMBING SEC. 912.1.1 (SEE DEFINITION OF |
| | BATHROOM GROUP). THE URINAL SHALL BE INDIVIDUALLY |
| | VENTED. |
| | 7) SHT.P4.01 - RISER S/2 - POINT "P" - THE VENT FROM |
| | THE STACK IS SHOWN AS 3 INCH, REDUCES TO 2 INCH AND |
| | THEN INCREASES TO 3 INCH AT THE CONNECTION TO RISER S/2 |
| | ON SHT.P4.03 - CLARIFY. |
| | 8) SHT. P4.03 - RISER S/14 - 13TH FLOOR TOILET ROOM |
| | #1305 BY STAIRS #2 - THE SANITARY RISER DOES NOT COMPLY |
| | WITH 2014 FBC-PLUMBING SECS.912 OR 914 FOR A HORIZONTAL |
| | WET VENT OR A CIRCUIT VENT.PLACING AN INDIVIDUAL VENT |
| | ON THE FIRST WATER CLOSET CONNECTED TO THE HORIZONTAL |
| | DRAIN WILL CORRECT THIS ISSUE. |
| | 9) SHT. P4.03 - 7TH FLOOR KING SUITE - ONLY 4 FIXTURE |
| | UNITS ARE PERMITTED ON A 2 INCH WET VENT PER 2014 |
| | FBC-PLUMBING SEC.912.3 & TABLE 912.3. SEE FLOORS #7- |
| | #12. |
| | 10) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS, |
| | COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS |
| | SHALL BE PROTECTED AGAINST BACKFLOW PER 2014 |
| | FBC-PLUMBING SECS.608.16.1 & 608.16.10. I COULD NOT |
| | FIND THE NOTE ON THE PLAN. CLARIFY. |
| | 11) SHT. P4.07 - DETAILS "A" &"B" - BOTH WATER RISERS |
| | INCLUDE "TYPICAL KING ROOM" VERBIAGE - CLARIFY. |
| | 12) SHT. P4.07 - DETAIL "B" - IF THIS WATER RISER IS |
| | SUPPOSED TO BE THE "KING SUITE" A WATER CLOSET IS |
| | MISSING FROM THE RISER IN THE HALF BATH AND A LAVATORY |
| | IS MISSING FROM THE RISER IN THE FULL BATH. |
| | 13) SUBMIT A CCOMPLETE WATER RISER FOR THE LAUNDRY |
| | ROOM.WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 14) PLACE A NOTE ON THE SANITARY DRAWINGS THAT ALL |
| | FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP PRIMERS. I |
| | CANNOT FIND THE NOTE AS STATED IN THE NARRATIVE. 2014 |
| | FBC-PLUMBING SEC.1002.4. |
| | 15) THE FUNNEL DRAINS RECEIVING THE DISCHARGE FROM THE |
| | ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS. |
| | 2014 FBC-PLUMBING SEC.1002.4. |
| | |