| 2016-12-14 16:28:42 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16061443 |
| | ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-718-5987 / MARGARET LEON |
| | E-MAIL: MLEONDADLP.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC.13/2016 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. 13 STORIES INCLUDING THE HABITABLE POOL, |
| | POOL DECK AND A2 DELI/ RESTAURANT AREAS. |
| | |
| | 2) NOTICE: ART IN PUBLIC PLACES. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER |
| | ART IN PUBLIC PLACES COORDINATOR |
| | TEL: 822-1515 |
| | E-MAIL: [email protected] |
| | WEBSITE: WPB.ORG/AIPP/ |
| | |
| | |
| | 3) 2ND REQUEST, TO BE SUBMITTED WHEN CONTRACTOR SUBMITS |
| | FOR PERMIT. THIS MAIN BUILDING PERMIT WILL INCLUDE THE |
| | FEES FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING |
| | PERMITS. WHEN THE GENERAL CONTRACTOR COMES IN FOR A |
| | BUILDING PERMIT WITH THE SIGNED PERMIT APPLICATION FORM |
| | BY THE QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| | IRRIGATION, TEST PILE, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR |
| | VALUE FROM THE OVERALL BUILDING VALUE OF |
| | $33,000,000.00. THE REMAINING BALANCE WILL BE |
| | AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE |
| | PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO |
| | COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| | COVERED UNDER THE PRIME OR MASTER PERMIT. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 108.3 BUILDING PERMIT VALUATION. |
| | |
| | 4) SEMI-COMPLIED. PLEASE SHOW COMPLIANCE BY THE 2014 |
| | FBC-ENERGY CODE. SEE MECHANICAL COMMENTS, THERE ARE |
| | NUMEROUS OMISSIONS AND INCONSISTENCIES SEE MECH. |
| | COMMENT # 1. |
| | |
| | 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 5A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | |
| | 5B) SEMI-COMPLIED. THE SUBMITTED FORMS WERE |
| | SEMI-COMPLETED, SHEET 3 OF 6 MISSING THE SPECIAL |
| | INSPECTOR SIGNATURE, DATE AND NOTARY NOTED SEE PREVIOUS |
| | PAGE. SIGNATURE FROM THE SPECIAL INSPECTOR PAGE 3 OF 6 |
| | AND HAVE THE JOBSITE INSPECTOR REFILE THE FORM SO ALL |
| | THE SIGNATURES ARE ON THE SAME SHEET. |
| | SHEET 5 OF 6 THERE IS NO CONTRACTOR SIGNATURE NOR |
| | NOTARY WORK COMPLETED. THIS SHEET WE WILL ACCEPT THE |
| | BOTTOM SIGNATURE AND SEAL OF THE ENGINEER OF RECORD. |
| | THRESHOLD INSPECTOR FORMS: WPB AMENDMENT 109.3.6.2 |
| | W.P.B. CONSTRUCTION SERVICES DEPARTMENT. |
| | |
| | |
| | 5C) COMPLIED. ARCHITECTURAL AND STRUCTURAL SHEETS. |
| | THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.3.7.4.4/ 633 FLORIDA STATUTE. |
| | |
| | 5D) THE SPECIAL INSPECTORS ONSITE REPRESENTATIVE MARK |
| | PINA HAS PRODUCED A RESUME? BUT THE RESUME DOES NOT |
| | INCLUDE ANY POST TENSION SLAB INSPECTION HISTORY. |
| | BEFORE THIS INSPECTOR CAN BE APPROVED AS THE PRIMARY |
| | JOBSITE INSPECTOR, THERE WILL NEED TO SHOW A HISTORY OF |
| | THIS TYPE OF INSPECTION. 61G15-35.004. |
| | |
| | WILL THERE BE MORE THAN ONE REPRESENTATIVE FROM THE |
| | ENGINEERING COMPANY DOING THE STRUCTURAL THRESHOLD |
| | INSPECTIONS? |
| | |
| | |
| | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | |
| | 5E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THRESHOLD INSPECTION FORMS , GUIDELINES AND POLICIES |
| | FOR PROJECTS WERE E-MAILED TO: |
| | [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME |
| | BACK UNDELIVERABLE. 07/14/2016 11:35 AM. |
| | [email protected] |
| | |
| | 5F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| | PRINT MAYBE IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 5G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING |
| | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | 5H) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 5H) INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD |
| | BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 6) 2ND REQUEST, IN THE PROCESS OF EITHER UNITY OF TITLE |
| | OR REPLAT. SHEET C-01 INDICATES THE PROPOSED SITE IS |
| | MADE UP OF 4 LOTS. UNDER THE 2014 FBC-B TABLE 602, |
| | BUILDINGS CANNOT BE BUILT OVER PROPERTY LINES. EITHER A |
| | REPLAT OF THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF |
| | TITLE. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| | COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| | FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| | PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS. |
| | BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| | HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| | NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| | ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| | |
| | 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE |
| | PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY |
| | CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE |
| | GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE |
| | FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH |
| | TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE |
| | SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| | WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| | SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| | WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| | IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| | BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE |
| | WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED? |
| | |
| | 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS |
| | SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 |
| | MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY |
| | OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL |
| | TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT |
| | ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE |
| | LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE. |
| | |
| | 10) COMPLIED. POLLUTION PREVENTION PLAN. 2014 FBC-B |
| | 3307. |
| | |
| | 11) PROVISO: DEFERRED SUBMITTAL . 2014 FBC-B 3306.9 |
| | ADJACENT TO EXCAVATIONS. STRUCTURAL NOTES S1.01. |
| | |
| | 11A) PROVISO: DEFERRED SUBMITTAL. STRUCTURAL NOTES |
| | S1.01 AND SOILS REPORT BY LANGAN ENGINEERING SOILS |
| | REPORT MAY 21/ 2015. 2014 FBC-B 3307.1 PROTECTION |
| | REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL |
| | BE PROTECTED FROM DAMAGE DURING CONSTRUCTION AND |
| | DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR |
| | FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS |
| | AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW |
| | WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM |
| | SETTLEMENT? |
| | |
| | 11B) COMPLIED. NOTED ON PLAN. 2014 FBC-B 3307.1 THE |
| | PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL |
| | PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| | BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| | MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| | PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| | LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| | OF THE EXCAVATION. |
| | |
| | 12) COMPLIED. NOTED ON PLAN. WHEN EXCAVATING WILL THE |
| | EXCESS SOILS BE STORED ON SITE? 2014 FBC-B 3304.1.2 |
| | SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS SHALL BE |
| | PLACED ADJACENT TO ANY BUILDING OR STRUCTURE UNLESS |
| | SUCH BUILDING OR STRUCTURE IS CAPABLE OF WITHSTANDING |
| | THE ADDITIONAL LOADS CAUSED BY THE FILL OR SURCHARGE. |
| | EXISTING FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED |
| | BY ANY EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR |
| | OTHERWISE PROTECTED AGAINST SETTLEMENT AND SHALL BE |
| | PROTECTED AGAINST LATER MOVEMENT. |
| | |
| | 13-19) COMPLIED. |
| | |
| | 20) SHEET A0.01; |
| | 20A)COMPLIED. |
| | |
| | 20B) SEMI- COMPLIED. THE RESPONSE INDICATED SEE REVISED |
| | SHEET M0.00 FOR THE BUILDING THERMOS INSULATION FOR |
| | EXTERIOR WALLS AND FOR THE ROOF. THE MINIMUM FOR THE |
| | ROOF IS STATED AS A R-19. THE POOL DECK (SHEET A2.10) |
| | NOR THE INTERSTITIAL SPACE (SHEET A2.09) ABOVE THE |
| | HIGHEST AIR CONDITIONED FLOOR SHOW INSULATION |
| | SEPARATING THE NON-CONDITIONED SPACE FROM AIR |
| | CONDITIONED SPACE. 2014 FBC-ENERGY CODE C402.2.5 FLOORS |
| | OVER OUTDOOR AIR OR UNCONDITIONED SPACE. |
| | |
| | |
| | |
| | 20C) SEMI ?COMPLIED. THE INTENT OF THIS COMMENT WAS TO |
| | STATE WHEN LOCATED OUTSIDE OF THE HIGH VELOCITY |
| | HURRICANE ZONE WE CANNOT ENFORCE THE REQUIREMENTS OF |
| | THE HIGH VELOCITY HURRICANE ZONE. ONLY BROWARD AND |
| | MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY HURRICANE |
| | ZONE. |
| | THE CITY OF WEST PALM BEACH ACCEPTS BOTH PRODUCT |
| | APPROVALS FROM THE STATE OF FLORIDA APPROVAL SYSTEM AND |
| | THE MIAMI-DADE NOAS. |
| | |
| | |
| | 1ST ROUND OF COMMENTS. UNDER THE HEADING BUILDING |
| | MATERIALS THE STATEMENT STATES ALL APPROVALS FOR |
| | WINDOWS AND DOORS ARE REQUIRED TO BE APPROVED BY |
| | MIAMI/DADE COUNTY REQUIREMENTS FOR HIGH VELOCITY |
| | HURRICANE ZONE REQUIREMENTS. PLEASE NOTE ONLY BROWARD |
| | AND MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY |
| | HURRICANE ZONE. SEE DEFINITIONS UNDER 202. |
| | HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF |
| | BROWARD AND DADE COUNTIES. |
| | |
| | 20D) BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW |
| | CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER |
| | THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND |
| | DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE |
| | SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE. |
| | 107.3.4.2 DEFERRED SUBMITTALS. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS, MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, |
| | INTAKE AND EXHAUST FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G PRE-ENGINEERED A/C STANDS |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 20E) BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT |
| | APPROVALS & SHOP DRAWINGS. |
| | IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 20F) 2ND REQUEST. ROOFING: FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED FOR ROOF ZONES 2 & 3. IF SO RAS 117 |
| | CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT |
| | OR ENGINEER. PLEASE ALSO PROVIDE A SHOP DRAWING FOR THE |
| | TAPERED ROOF INSULATION SHOWING COMPLIANCE WITH A |
| | MINIMUM VALUE OF R-19 ( NOT AN AVERAGED VALUE). |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR |
| | ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |
| | 21A) 2ND REQUEST. SHEET A1.01.THE REVISED SITE PLAN |
| | SHOWS 72 PARKING SPACES. SHEET A2.03 THERE IS 26 |
| | SPACES, SHEET A2.04 ANOTHER 26 SPACES AND SHEET A2.05 |
| | 22 SPACES OR A TOTAL OF 74 SPACES. PLEASE CORRECT THE |
| | TOTAL COUNT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | 21B) ON SHEET A2.05 THE PLANS SHOW A TOTAL OF 3 |
| | ACCESSIBLE PARKING SPACES. WITH THE LOCATION OF THE 2 |
| | SPACES LOCATED ON THE EXTERIOR WALL AND THE ENTRY INTO |
| | THE ELEVATOR LOBBY ONE OF THE ACCESSIBLE PARKING SPACES |
| | REQUIRES THE OCCUPANT TO HAVE TO TRAVEL BEHIND PARKED |
| | CARS. |
| | 2014 FBC-ACCESS. CODE 208.3.1. PARKING SPACES COMPLYING |
| | WITH 502 THAT SERVE A PARTICULAR BUILDING OR FACILITY |
| | SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM |
| | PARKING TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES |
| | MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST |
| | 44 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT |
| | COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES |
| | EXCEPT BEHIND HIS OR HER OWN VEHICLE. |
| | |
| | 1ST ROUND OF COMMENTS. SITE PLAN A1.01 INDICATES THERE |
| | ARE 79 PARKING SPACES WITHIN THE BUILDING. SHEET A1.15 |
| | THE 5TH FLOOR LIFE SAFETY PLAN THE 3RD PARKING LEVEL |
| | SHOWS A TOTAL OF 4 ACCESSIBLE PARKING SPACES, OF THE 4 |
| | ACCESSIBLE PARKING SPACES, (1) SPACE NEEDS TO COMPLY |
| | WITH THE VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS. |
| | CODE 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE |
| | 1ST FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND |
| | THE VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5. |
| | ADVISORY 502.5 VERTICAL CLEARANCE. |
| | SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES |
| | INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN |
| | ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER |
| | ASSISTANCE. |
| | |
| | FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED |
| | THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF |
| | HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT |
| | WHERE THE VAN CANNOT BE MANEUVERED. |
| | |
| | FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT |
| | RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE |
| | WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION. |
| | ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT |
| | PROHIBITS A COVERED ENTITY FROM COMPLYING WITH |
| | REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN |
| | VIOLATION OF THE ADA. |
| | |
| | 22) COMPLIED. VAN ACCESSIBILITY. 2014 FBC-ACCESS. 502.6 |
| | IDENTIFICATION. |
| | |
| | 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| | A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE |
| | FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING |
| | FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED |
| | THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON |
| | A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER |
| | FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS |
| | ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON |
| | THE 1ST FLOOR. |
| | |
| | 23B)SEMI- COMPLIED. LIFE SAFETY SHEET A1.THE OCCUPANCY |
| | LOAD SHOWN FOR THE 2ND FLOOR OF 569. THE CODE ANALYSIS |
| | INDICATES THERE ARE 2 STAIRS AT 57 INCHES WHICH WILL |
| | ACCEPT 190 OCCUPANTS NOT 206. THE 3RD STAIR IS LABELED |
| | AS 52 INCHES WIDE. THE 600 SERIES PLANS FOR STAIRS IT |
| | APPEARS ALL 3 STAIRS ARE 57 INCHES WIDE. 57/0.3= 190 |
| | OCCUPANTS X 3 STAIRS= 570 OCCUPANTS. AGREED THE STAIRS |
| | APPEAR TO BE THE LIMITING FACTOR. |
| | TO USE THE 57/0.2 FACTOR NOT ONLY DOES THE BUILDING |
| | REQUIRE FIRE SPRINKLERS BUT COMPLIANCE WITH AN |
| | EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM. |
| | |
| | 23C)(1 & 2) COMPLIED. |
| | |
| | 23D-G) COMPLIED. |
| | |
| | 24A) COMPLIED. |
| | |
| | 24B) COMPLIED. SHEET A1.12 LIFE SAFETY 3 STAIRS ARE A |
| | MINIMUM OF 57 INCHES/ 0.3= 190 OCC. X 3= 570 OCCUPANTS. |
| | |
| | 24C) COMPLIED. CONFERENCE ROOMS 2 MEANS OF EGRESS. |
| | |
| | 24D) 2ND REQUEST . SEMI-COMPLIED. SHEET FP2.02 SHOWS |
| | THE USE OF TYCO WINDOW SPRINKLERS, IT APPEARS THAT (2) |
| | SPRINKLERS ARE LOCATED ON THE VERTICAL MULLION. PLEASE |
| | PROVIDE A DETAIL FOR SPRINKLER AND WASHING OF THE |
| | GLAZING FOR THIS AREA. 404.6 EXCEPTION 1.1. |
| | |
| | 1ST REVIEW COMMENTS. THERE IS A NOTE FOR S SMOKE |
| | PARTITION FOR THE 2 STORY ATRIUM USING THE EXCEPTION #1 |
| | REQUIRING BOTH REQUIREMENTS OF 404.6 EXCEPTION 1.1 & |
| | 1.2 BE MET. PLEASE PROVIDE DETAILS FOR THE SPACING OF |
| | THE FIRE SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE |
| | GLASS WALL SHALL BE INSTALLED IN A GASKETED FRAME IN A |
| | MANNER THAT THE FRAMING SYSTEM DEFLECTS WITHOUT |
| | BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLER |
| | SYSTEM OPERATES. |
| | |
| | 24E) COMPLIED. |
| | |
| | 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03, |
| | THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD, 4TH |
| | AND 5TH FLOORS. |
| | |
| | 25A)(1) COMPLIED. FBC-B 3007.7.2. THE FIRE SERVICE |
| | ACCESS ELEVATOR LOBBY . SECTION 3007.7.3. |
| | |
| | 25A)(2) NEW COMMENT, DESIGN ISSUE, NOT A CODE ISSUE. |
| | THE ACCESSIBLE PARKING SPACES ARE FOUND ON THE 5TH |
| | FLOOR PARKING. TO GAIN ACCESS TO ANY OF THE FLOORS A |
| | WHEELCHAIR BOUND PERSON WILL NEED TO USE THE FIREMEN?S |
| | ELEVATOR. IF THE BUILDING GOES INTO FIRE ALARM THE |
| | ACTUATION OF ANY BUILDING FIRE ALARM-INITIATING DEVICE |
| | SHALL INITIATE PHASE I EMERGENCY RECALL OPERATION ON |
| | ALL FIRE SERVICE ACCESS ELEVATORS IN ACCORDANCE WITH |
| | THE REQUIREMENTS IN ASME A17.1/CSA B44. THE OCCUPANT IN |
| | THE FIREMEN?S LOBBY ELEVATOR WILL BE STRANDED WITHOUT |
| | ANY MEANS OF COMMUNICATION!!!! |
| | AS YOU KNOW THE 2014 ACCESSIBILITY CODE SECTION 207.1 |
| | REFERS YOU IN THE 2003 IBC TO SECTION 1007 FOR |
| | ACCESSIBLE MEANS OF EGRESS. IN SECTION 1007.6 IS THE |
| | SECTION FOR AREAS OF REFUGE. SECTION 1007.3 EXCEPTION 2 |
| | AREAS OF REFUGE ARE NOT REQUIRED IN BUILDINGS THAT ARE |
| | EQUIPPED THROUGHOUT IN ACCORDANCE WITH SECTION |
| | 903.3.1.1. |
| | |
| | 25B-D) COMPLIED. |
| | |
| | 25E) SEMI-COMPLIED. A6.12 NOW DOES SHOW VERTICAL |
| | BI-PARTING DOORS. THERE IS NO DOOR IDENTIFICATION TAG |
| | PROVIDED, NEITHER IS THERE INFORMATION ON THIS DOOR AS |
| | FAR AS HOURS OF RATING. THIS IS A 5 STORY SHAFT |
| | REQUIRING 2 HR. RATING OF WALLS AND 90 MINUTE OPENING |
| | PROTECTIVES, TABLE 716.5 OF THE 2014 FBC-B. |
| | 1ST ROUND OF COMMENTS. THIS COMMENT IS A COMMON FOR THE |
| | 3 PARKING FLOORS AND THE 1ST FLOOR. THE PLANS INDICATE |
| | TO PROVIDE FALL PROTECTION AT THE ENTRY OF THE |
| | AUTOMOBILE ELEVATOR. PLEASE PROVIDE COMPLIANCE WITH |
| | 2014 FBC-B 1013.2 GUARDS SHALL BE LOCATED ALONG |
| | OPEN-SIDED, EQUIPMENT PLATFORMS, STAIRS, RAMPS AND |
| | LANDINGS THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) |
| | MEASURED VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY |
| | POINT WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE |
| | EDGE OF THE OPEN SIDE. GUARDS SHALL BE ADEQUATE IN |
| | STRENGTH AND ATTACHMENT IN ACCORDANCE WITH SECTION |
| | 1607.8. |
| | |
| | 25F) COMPLIED. 1607.8.3 VEHICLE BARRIERS. |
| | |
| | 25G)SEMI-COMPLIED. DEPENDING ON THE NEW LOCATION OF |
| | COMMENT (21D). SHEET A2.05 LIFE SAFETY PLAN INDICATES 2 |
| | ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS |
| | AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN |
| | TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE |
| | 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN |
| | PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE |
| | MINIMUM. |
| | |
| | 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 & |
| | A7.06 ENLARGED FLOOR PLAN 6TH FLOOR. |
| | |
| | 26A-E) COMPLIED |
| | |
| | 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR |
| | TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11. |
| | ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR |
| | TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11. |
| | ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 26H) WE NEED A LETTER ADDRESSED TO THE BUILDING |
| | OFFICIAL ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT |
| | BROWN UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION SECTION 104.11 ALTERNATE |
| | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION. MR. |
| | BROWN HAS ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED |
| | THE LETTER TO BE SUBMITTED REQUESTING THE ALTERNATE |
| | DESIGN IN MEETING THE CODE REQUIREMENT. |
| | |
| | ** COMMON COMMENT FOR ALL FLOORS (7-12) WHERE THE |
| | ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE: |
| | ROOMS 718 & 719 FROM THE MOST REMOTE POINT IN THE SUITE |
| | TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75 |
| | FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS |
| | INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR |
| | SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A |
| | CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED |
| | CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION: |
| | COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT |
| | ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE |
| | BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL |
| | TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON |
| | PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE |
| | INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE. |
| | |
| | 27) WE NEED A LETTER ADDRESSED TO THE BUILDING OFFICIAL |
| | ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT BROWN |
| | UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION SECTION 104.11 ALTERNATE MATERIALS, |
| | DESIGN AND METHODS OF CONSTRUCTION. MR. BROWN HAS |
| | ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED THE LETTER |
| | TO BE SUBMITTED REQUESTING THE ALTERNATE DESIGN IN |
| | MEETING THE CODE REQUIREMENT. |
| | |
| | MR. BROWN HAS LOOKED AT THE ADDITIONAL COST INVOLVED IN |
| | THE 2 HR. RATING OF THE WHOLE CORRIDOR AND 1 1/2 HOUR |
| | RATING OF ALL DOORS WITHIN THE CORRIDOR. |
| | |
| | MR. BROWNS SUGGESTION IS TO CREATE A 2 HOUR VESTIBULE |
| | IN FRONT OF STAIRWELL NUMBER ONE. LEAVE THE 1 ? HOUR |
| | DOOR FOR THE STAIRWELL AND EXTEND THE 2 HOUR FIRE |
| | RATING TO JUST WEST OF THE ROOMS 715 & 722, A PAIR OF |
| | DOORS, SWING THE DOORS IN THE EGRESS TRAVEL AND HAVE |
| | THE DOORS ON HOLD OPENS. TO THE WEST OF THE STAIRWELL 1 |
| | DOOR OPENING HAVE A SECOND PAIR OF DOORS ON HOLD OPENS |
| | IN LINE WITH UNITS 713 & 714, ON THE OPPOSITE WALL IT |
| | APPEARS A FIRE EXTINGUISHER CABINET WOULD HAVE TO BE |
| | RELOCATED. THIS DESIGN WOULD HOLD TRUE FOR THE FLOORS |
| | 7-12. FLOOR 6 WE MEET THE TRAVEL DISTANCE SINCE THE |
| | STAIRWELL # 1 WAS EXTENDED WITH THE 2ND REQUIRED DOOR |
| | OPENING. |
| | |
| | SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH |
| | FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018, |
| | 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT. |
| | ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B |
| | TABLE 1014.3 |
| | |
| | 28) COMPLIED. |
| | |
| | 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN: |
| | 29A-D) COMPLIED. |
| | |
| | 29E) 2ND REQUEST. THE INTERIOR LOBBY/ DINING AREA SHOWS |
| | 36 INDOOR SEATS AT TABLES NOT 26. 36X0.05= 1.8 OR (2) |
| | SEATS, COMPLIED. |
| | THE AREA OF NON-COMPLIANCE IS THE OUTDOOR LOUNGE AREA |
| | SHOWS TABLES AND 20 CHAIRS REQUIRING AT LEAST (1) |
| | ACCESSIBLE SEAT. 20X0.05= 1 |
| | 1ST ROUND OF COMMENTS. THE AREAS ROOF LOUNGE AND LOBBY, |
| | 1313 & 1314 MAY NEED TO COMPLY WITH ACCESS. CODE 902.3 |
| | IF THERE ARE TABLES PRESENT. THIS PLAN DOES NOT SHOW A |
| | SEATING ARRANGEMENT IN THE ROOF LOUNGE 1314. |
| | |
| | 29F) 2ND REQUEST. STAIRWELL # 1 SHOWS A ROOF TOP HATCH |
| | FOR ACCESS TO THE UPPER ROOF WITH MECHANICAL EQUIPMENT |
| | ON THE ROOF TOP. PLEASE PROVIDE THE CLEAR OPENING FOR |
| | THE ROOF TOP ROOF HATCH AND COMPLIANCE WITH 2014 FBC-B |
| | SECTION 1009.16.1 EXCEPTION. IN BUILDINGS WITHOUT AN |
| | OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO |
| | BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE |
| | FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET . |
| | |
| | 1ST ROUND COMMENTS. STAIRWELL # 1 SHOWS A LADDER TO |
| | GAIN ACCESS TO THE ROOF TOP EQUIPMENT. 2014 FBC-B |
| | SECTION 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| | RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR |
| | EXIT STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED |
| | EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| | FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| | SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| | |
| | 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL |
| | REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. |
| | |
| | 31) BUILDING PROVISO. FENCING AND GATES AROUND THE POOL |
| | WILL REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED |
| | FEES. |
| | |
| | 32) COMPLIED. |
| | |
| | 33-34) COMPLIED. |
| | |
| | 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02 |
| | & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION |
| | 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| | REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR |
| | CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH. |
| | THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL |
| | DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE |
| | PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF |
| | CONCERN: |
| | |
| | 36A) 2ND REQUEST. SHEET A4.01 THERE IS A NOTE |
| | INDICATING THE MATERIAL ON THE UNDERSIDE OF THE CANOPY |
| | IS A CLADDING PANEL COMPOSITE. PLEASE PROVIDE THE |
| | LITERATURE ON THIS PRODUCT, IF THE PRODUCT DOES NOT |
| | MEET THE DEFINITION OF COMPOSITE THEN CHANGE THE |
| | TERMINOLOGY, BUT PRODUCT INFORMATION IS STILL GOING TO |
| | BE REQUIRED. PLEASE PROVIDE THE PRODUCT APPROVAL |
| | MIAMI-DADE NOA 15-0211.05 FOR REVIEW FOR WIND PRESSURES |
| | AS WELL AS FOR FLAME SPREAD AND SMOKE DEVELOPMENT. |
| | 1ST ROUND OF COMMENTS. THE NOTE FOUND ON A4.01 |
| | INDICATES THE UNDERNEATH SIDE OF THE CANOPY IS TO BE |
| | FINISHED WITH A WOOD COMPOSITE MATERIAL. WE FIND THIS |
| | SAME NOTE AT AROUND THE 155 FT. & 173.5 FT. ELEVATION. |
| | PLEASE PROVIDE PRODUCT LITERATURE ON THIS PRODUCT TO |
| | SEE HOW THIS MATERIAL WAS TESTED, TO WHAT STANDARD? |
| | DOES IT MEET THE DEFINITION OF A COMPOSITE MATERIAL. |
| | |
| | DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE |
| | MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF |
| | NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE |
| | WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN |
| | 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD |
| | INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS |
| | NONCOMBUSTIBLE MATERIALS. |
| | |
| | 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV |
| | CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE |
| | PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS, |
| | COMPLYING WITH THE FOLLOWING LIMITATIONS: |
| | 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED |
| | 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE |
| | FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS. |
| | 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED |
| | TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE. |
| | 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION |
| | 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED |
| | IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE |
| | IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP |
| | TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE |
| | REGARDLESS OF THE FIRE SEPARATION DISTANCE. |
| | 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5. |
| | 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR |
| | FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524 |
| | MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT |
| | HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT |
| | HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD |
| | WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE |
| | SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL |
| | COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2 |
| | BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT |
| | RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING |
| | OF THE EXTERIOR WALL COVERING. |
| | |
| | 36B) 2ND REQUEST. THE RESPONSE INDICATES A NEW SHEET |
| | A5.15 EYEBROW DETAILS 1-6 ALL SHOW THE RESYSTA CP 140 |
| | COMPOSITE CLADDING PANEL AND ATTACHMENT OF THE PANELS |
| | PER THE NOA, BUT NO INFORMATION IS PROVIDED AS TO THE |
| | MECHANICAL ATTACHMENT OF THE 1 X 3 TO THE CONCRETE |
| | EYEBROW. |
| | 1ST ROUND OF COMMENTS. THE WOOD COMPOSITE MATERIAL, |
| | PLEASE PROVIDE HOW THIS MATERIAL WILL BE ATTACHED TO |
| | THE SUB-STRUCTURE, ADHERED, PINNED? 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 36C) PROVISO: POLYMER MODIFIED CEMENT WATER PROOFING TO |
| | THE TOP OF THE CONCRETE EYEBROW. SUBMIT PRODUCT |
| | APPROVAL. TO BE REVIEWED BY THE DESIGNER OF RECORD |
| | BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT. |
| | |
| | 37) BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01 |
| | THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE |
| | PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE |
| | PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF |
| | THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING |
| | SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL |
| | BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE |
| | BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS |
| | OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND |
| | INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED |
| | MANUFACTURERS INSTRUCTIONS SUCH THAT THE ROOF COVERING |
| | SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. |
| | |
| | |
| | 38A) COMPLIED. FIRE COMMAND CENTER LAYOUT. FBC-B |
| | 911.1.4. |
| | |
| | 38B) SEMI-COMPLIED) 911.1.5 REQUIRED FEATURES. |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND |
| | SHALL CONTAIN THE FOLLOWING FEATURES: |
| | |
| | 1.-5) SHEET E4.02 |
| | 6. 2ND REQUEST, SEMI-COMPLIED. PLEASE REVIEW THE |
| | MECHANICAL PLANS REVIEW COMMENT # 3, 2ND REVIEW. |
| | THE FIREFIGHTERS CONTROL PANEL REQUIRED BY SECTION |
| | 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE |
| | BUILDING. |
| | |
| | 7-12). SHEET E4.02. |
| | |
| | 13) BUILDING PROVISO/ DEFERRED SUBMITTALS. (13.1-13.7) |
| | AN APPROVED BUILDING INFORMATION CARD THAT CONTAINS, |
| | BUT IS NOT LIMITED TO, THE FOLLOWING INFORMATION: |
| | |
| | 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES: |
| | PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE |
| | BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY |
| | CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT |
| | TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING |
| | POPULATION (I.E., DAY, NIGHT, WEEKEND); |
| | |
| | 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT |
| | INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS |
| | (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND |
| | THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER, |
| | EMAIL ADDRESS; |
| | |
| | 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES: |
| | THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS, |
| | COLUMNS, AND ROOF ASSEMBLY); |
| | |
| | 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF |
| | EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION |
| | AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR |
| | DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT |
| | STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT |
| | STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF |
| | ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF |
| | ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR |
| | NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION |
| | OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY, |
| | LOCATION OF FREIGHT ELEVATOR BANKS; |
| | |
| | 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT |
| | INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF |
| | BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF |
| | ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR, |
| | LOCATION OF NATURAL GAS SERVICE; |
| | |
| | 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES: |
| | LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM, |
| | LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS |
| | PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF |
| | DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G., |
| | DRY, WET, PRE-ACTION, ETC.); AND |
| | |
| | 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES: |
| | LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS |
| | MATERIAL. |
| | |
| | 14. WORK TABLE. |
| | |
| | 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| | TRANSFER FEATURES. |
| | |
| | 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE. |
| | |
| | 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | |
| | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED. |
| | |
| | 39) COMPLIED. 2014 FBC-B 403.5.3 STAIRWAY DOOR |
| | OPERATION. |
| | |
| | 40) SEMI ?COMPLIED. PLEASE REVIEW THE MECHANICAL PLANS |
| | REVIEW COMMENT # 3, 2ND REVIEW. 2014 FBC-B 403.4.7 |
| | SMOKE REMOVAL./ 909.4 ANALYSIS. A RATIONAL ANALYSIS |
| | SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE |
| | EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS |
| | SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE |
| | UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION |
| | DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| | ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. |
| | |
| | 41) COMPLIED. FBC-B 403.5.5 LUMINOUS EGRESS PATH |
| | MARKINGS.. |
| | |
| | 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 43) COMPLIED, THANK YOU. FOR THE RESUBMISSION OF PLANS, |
| | PLEASE BREAK THE PLAN SETS DOWN TO SMALLER MANAGEABLE |
| | ROLLS. BUILDING AND ID DRAWINGS TOGETHER, STRUCTURAL BY |
| | ITSELF AND MEP TOGETHER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |