| 2016-08-14 08:49:55 | 1) CIVIL DRAWING C-10 SHOWS A 1500 GALLON GREASE |
| | INTERCEPTOR AND PLUMBING SHEET P5.06 CALLS OUT A 1250 |
| | GALLON INTERCEPTOR. CLARIFY. |
| | 2) LANDSCAPE DRAWINGS - SHOW THE SOURCE OF WATER FOR |
| | THE IRRIGATION SYSTEM AND THE LOCATION OF THE |
| | IRRIGATION SYSTEM CONTROLLER AND THE RAIN SENSOR. WPB |
| | AMEND TO FBC SEC. 107.2.1. |
| | 3) SUBMIT THE OCCUPANT LOAD FOR THE DIFFERENT |
| | OCCUPANCIES (ASSEMBLY- A-2, A-3, BUSINESS, STORAGE, |
| | ETC.). THIS INFORMATION IS NEEDED TO DETERMINE THE |
| | MINIMUM REQUIRED SANITARY FACILITIES FOR THE DIFFERENT |
| | OCCUPANCY GROUPS FOR THE COMMON AREAS PER THE 2014 FPC |
| | TABLE 403.1. |
| | 4) THE ASSEMBLY AREAS MAY BE REQUIRED TO COMPLY WITH |
| | THE POTTY PARITY REQUIREMENTS OF THE 2014 FPC SEC. |
| | 403.1.3. |
| | 5) PLACE A NOTE ON THE ARCHITECTURAL PLANS THAT THE |
| | GENERATOR & FUEL PIPING WILL BE DONE UNDER A SEPARATE |
| | PERMIT. |
| | 6) SHT. A0.01 NOTES THIS BUILDING IS A 6 STORY MIDRISE |
| | BUT THE APPLICATION NOTES THAT IT IS A 17 STORY |
| | BUILDING. IT APPEARS TO BE A 13 STORY BUILDING. |
| | CLARIFY. |
| | 7) SHT. A2.09 REFERS TO DETAIL 4 ON SHT. A7.41 - THERE |
| | IS NO DETAIL 4 ON A7.41. CLARIFY. |
| | 8) SHT. A7.41 - DETAIL #13 - SHOWER HEAD LOCATION - A |
| | FIXED SHOWER HEAD MOUNTED AT 48 INCHES ABOVE THE FINISH |
| | FLOOR IS NOT PERMITTED IN TRANSIENT LODGING ROOMS PER |
| | THE 2014 FBC-ACCESS. SEC.608.6 EXCEPTION. |
| | 9) SHT. A7.41 - SEATS LOCATED IN THE HANDICAPPED |
| | ACCESSIBLE SHOWERS SHALL COMPLY WITH THE 2014 |
| | FBC-ACCESS. SECS. 610.3 & 806.2.4. SUBMIT COMPLETE |
| | DETAILS FOR THE TYPE OF SEAT (RECTANGULAR OR L-SHAPED,) |
| | DIMENSIONS FROM WALLS, LOCATION, ETC. |
| | 10) SHT. A7.41 - DETAIL #13 SHOWS THE MAXIMUM HEIGHT |
| | RANGE FOR THE ACCESSIBLE LAVATORY AS 3 FEET. THE |
| | MAXIMUM HEIGHT SHALL BE 34 INCHES. 2014 FAC SEC. 606.3. |
| | 11) SHT. A8.01 - SHOW THE WALL FINISH MATERIAL FOR |
| | ROOMS #130,131,142,210,211,212,621, & 622. COMPLY WITH |
| | THE 2014 FBC SEC. 1210. |
| | 12) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN. FAC |
| | SEC. 609.4. |
| | 13) SHT. A7.41 - ALTERNATE ROLL-IN SHOWER MEN'S & |
| | WOMEN'S LOCKER ROOM - THE CONTROLS FOR THE ALTERNATE |
| | ROLL-IN SHOWER SHALL COMPLY WITH 2014 FAC SECS. |
| | 608.5.3,608.6. THE THRESHOLD SHALL COMPLY WITH 608.7. |
| | 14) SHT. A7.41 - THE DETAILS SHOW ALL THE HANDICAPPED |
| | WATER CLOSETS AT A HEIGHT OF ONE FOOT THREE INCHES |
| | ABOVE THE FINISH FLOOR YET DETAIL #3 SHOWS ONE FOOT |
| | SEVEN INCHES. CLARIFY. |
| | 15) SHT. A7.41 - TOILET PAPER DISPENSERS SHALL BE |
| | LOCATED IN ACCORDANCE WITH THE FAC SEC.604.9.6. |
| | 16) SHT. A7.41 - DETAIL #6 - THE LENGTH OF THE STANDARD |
| | TOILET STALLS SHALL COMPLY WITH FBC-PLUMBING SEC.403. |
| | 17) SHT. ID-0.1 ADA GUIDELINES - THE ACCESSIBILITY CODE |
| | THAT IS IN EFFECT IN FLORIDA IS THE 2014 |
| | FBC-ACCESSIBILITY VOLUME, NOT THE ADA. THE FLORIDA CODE |
| | IS AN ADA EQUIVALENT CODE AND CERTIFIED BY THE DOJ. |
| | THESE DETAILS ARE NOT REQUIRED AND MAY CONFLICT WITH |
| | THE FBC. |
| | 18) SHT.ID-2.40 - DETAIL 03 & SHT.ID-4.30 - SHOWS A |
| | SINK LOCATED IN THE CORRIDOR. IF AVAILABLE TO THE |
| | GUESTS THIS SINK SHALL COMPLY WITH FBC-ACCESS. SECS. |
| | 305. 606. MAX. HEIGHT SHALL BE 34 INCHES. |
| | 19) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE ZOELLER |
| | ALARM FOR THE ELEVATOR SUMP PUMP. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 20) SHT. P-2.01 - SHOWS THE FIRE STANDPIPE DRAIN |
| | DISCHARGING TO THE STORM DRAINAGE SYSTEM. CITY CODE OF |
| | ORDINANCES ARTICLE V, SEC. 90-203 (A) PROHIBITS THE |
| | DISCHARGE OF ANYTHING OTHER THAN STORM WATER INTO THE |
| | STORM DRAINAGE SYSTEM. |
| | 21) LABEL THE GW WATER RISERS ON THE WATER DISTRIBUTION |
| | ISOMETRICS. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 22) SHT. P4.01 - GREASY WASTE RISER GR/1 SHOWS NO |
| | CONTINUATION POINT. CLARIFY. SUBMIT A COMPLETE |
| | RISER/COLLECTION SYSTEM FOR THE GREASE WASTE SYSTEM. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 23) SHT. P4.01 - SHOW THE CONTINUATION POINT FOR THE |
| | VENT FOR THE HAND SINK IN THE CAFE? (ROOM #134). |
| | 24) INDIVIDUAL VENTS, BRANCH VENTS, CIRCUIT VENTS AND |
| | RELIEF VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH |
| | SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE |
| | ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2014 FPC |
| | SEC.906.2. |
| | 25) SHT. P2.08 - KEYNOTE #16 - REFERS TO 3 INCH |
| | SANITARY TO LEVEL 6 AND STATES "SEE P2.06 FOR LAYOUT." |
| | P2.06 IS FOR THE FOURTH FLOOR. CLARIFY. |
| | 26) SHT. P2.09 - KEYNOTE #6 REFERS TO SHT. P2.01 FOR |
| | CONTINUATION. THIS LINE IS NOT SHOWN ON P2.01. CLARIFY. |
| | 27) SHT. P2.09 - 3 PD'S (62 SF, 18 SF, 18 SF) & 1 DD |
| | (1161 SF) AT GRID LINES 7-8 & B-C DO NOT APPEAR TO BE |
| | ON THE STORM RISER DRAWINGS. CLARIFY. |
| | 28) SHT. P2.12 - KEYNOTE #8 REFERS TO A GAS SOLENOID |
| | VALVE & SHUTOFF VALVE. THE VALVES SHALL BE LOCATED IN |
| | THE SAME ROOM AS THE APPLIANCE. 2014 FGC SEC.409.5.1. |
| | 29) SHT. P2.12 -KEYNOTE #11 REFERS TO SHTS.P4.04 & |
| | P4.06 FOR ENLARGED KITCHEN/BAR PLANS. THERE ARE NO SUCH |
| | ENLARGED PLANS ON THESE SHEETS. CLARIFY. |
| | 30) SHT. P2.12 - BOTTOM PLAN - KEYNOTE # 3 REFERS TO |
| | SHTS. P4.04 & P4.06 FOR GREASY WASTE PIPING. THERE IS |
| | NO GREASY WASTE PIPING ON THESE SHEETS. REVISE NOTE TO |
| | REFER TO CORRECT PAGE. |
| | 31) SHT. P2.12 - IDENTIFY ALL THE RISERS WITH A RISER |
| | IDENTIFYING TAG NUMBER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 32) SHT. P2.13 - BOTTOM PLAN - KEYNOTE # 9 - SHOW THESE |
| | RISERS ON P2.09 AS NOTED. I CANNOT FIND THESE RISERS ON |
| | P2.09.CLEARLY IDENTIFY THESE RISERS. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 33) SHT. P2.09 SHOWS A SANITARY AND WATER LINE IN |
| | STAIRWELL #1. THIS IS NOT PERMITTED PER 2014 |
| | FBC-BUILDING SEC. 1009.3.1.5.1. |
| | 34) SHT. P4.01 - THE PLANS SHOW THE WASTE FROM THE |
| | ELEVATOR SUMPS DISCHARGING INTO THE GREASY WASTE |
| | SYSTEM. THIS IS NOT PERMITTED. THE ELEVATOR SUMPS ARE |
| | EQUIPPED WITH ALARMS. THIS DISCHARGE CAN GO TO THE |
| | SANITARY OR TO A SEPARATE OIL SEPARATOR IF DESIRED. FBC |
| | 1003.3.1. |
| | 35) SHT. P4.01 - RESTROOMS #209 & 210 AND ROOMS #235, |
| | 236, 237 & 238 - THE RISER DOES NOT COMPLY WITH THE |
| | 2014 FPC FOR WET VENTS OR CIRCUIT VENTS. |
| | 36) A LINT INTERCEPTOR IS REQUIRED FOR THE LAUNDRY ROOM |
| | PER 2014 FPC SEC. 1003.6. |
| | 37) SHTS. P4.01 & P4.02 - CLEARLY IDENTIFY THE |
| | CONTINUATION POINTS OF ALL VENTS. |
| | 38) SHT. P4.02 - I CANNOT FIND KEYNOTE #1 ON THE PLAN. |
| | CLARIFY. |
| | 39) SHT. P4.02 - CLARIFY THE DESIGN OF THE FIRST LEVEL |
| | SANITARY SYSTEM. IT DOES NOT COMPLY WITH THE 2014 FPC |
| | SEC. 912 FOR WET VENTS OR SEC. 914 FOR CIRCUIT VENTING. |
| | 40) SHT. P4.02 - THE LAYOUT OF THE 5TH FLOOR SANITARY |
| | DOES NOT CORRELATE WITH THE FLOOR PLAN ON SHT. P2.08. - |
| | CLARIFY. |
| | 41) SHT.P4.02 - THE 1ST LEVEL RISER SHOWS A PIECE OF |
| | KITCHEN EQUIPMENT DISCHARGING INTO THE SANITARY. THEY |
| | SHALL DISCHARGE INDIRECTLY INTO THE GREASE WASTE |
| | SYSTEM. FPC SEC. 1003.3.1. |
| | 42) SHT. P4.02 - REFERS TO SHT. P5.01 FOR CONTINUATION |
| | OF SANITARY LINES AND VENTS. THERE ARE NO RISERS ON |
| | SHT. P5.01. CLARIFY. |
| | 43) SHT. P4.03 - RISER S/2 - KEYNOTE #3 - THE |
| | REFERENCED VENT IS NOT IDENTIFIED ON SHT. P4.02. |
| | CLARIFY. |
| | 44) SHT. P4.03 - RISER S/15 - THERE ARE NOT FIXTURES |
| | SHOWN ON THE STACK AND IT IS INCOMPLETE. PROVIDE THE |
| | ENTIRE RISER FOR REVIEW. |
| | 45) SHT. P4.03 - RISER S/14 - RESTROOMS BY STAIR #2 - |
| | THE RISER DOES NOT COMPLY WITH THE FPC SEC. 912 OR SEC. |
| | 914 FOR A HORIZONTAL WET VENT OR A CIRCUIT VENT. |
| | 46) SHT. P4.04 - KEYNOTE #2 REFERS TO SHT. P4.03 FOR |
| | THE CONTINUATION OF WATER LINES. SHT.P4.03 IS SANITARY |
| | RISERS. KEYNOTE #2 DOES CORRELATE WITH WHAT IS SHOWN ON |
| | THE WATER RISER. SEE KEYNOTES #3 & #8 ALSO. CLARIFY. |
| | 47) SHT. P4.05 - KEYNOTE #1 REFERS TO SHT. P4.03A. |
| | THERE IS NO SUCH SHEET. CLARIFY. |
| | 48) SHT. P4.05 - SIZE ALL SECTIONS OF THE WATER RISER. |
| | SEE KEYNOTE #1 AND PIPING AT POINTS A & B. |
| | 49) SHEET P4.05 - SHOW THE CONTINUATION POINTS OF THE |
| | "A" LINE. THE RISER APPEARS TO SHOW TWO LINES TURNED |
| | DOWN. |
| | 50) SHT. P4.05 - KEYNOTE #5 DOES NOT APPEAR TO |
| | CORRELATE WITH THE RISER. CLARIFY. |
| | 51) SHT. P4.05 - SHOW THE CONTINUATION POINT OF THE 140 |
| | DEGREE WATER. |
| | 52) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS, |
| | COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS |
| | SHALL BE PROTECTED AGAINST BACKFLOW PER FPC SECS. |
| | 608.16.1 & 608.16.10. |
| | 53) SUBMIT A WATER RISER FOR THE TYPICAL KING ROOM. THE |
| | WATER RISER ON P4.07 IS FOR THE KING SUITE. WPB AMEND. |
| | TO FBC SEC. 107.3.5.1.3. |
| | 54) SHT. P4.07 - DETAIL "C" THE WATER RISER SHOWS 2 |
| | LAVATORIES IN EACH ROOM & SHT. P2.10 AND RISER S/12 |
| | APPEAR TO SHOW ONE LAVATORY IN EACH ROOM. CLARIFY. |
| | 55) SHT. P4.07 - DETAIL 'H" - IDENTIFY THE L/SK & SK ON |
| | THE WATER RISER. IF THESE ARE IN THE LAUNDRY ROOM |
| | INCLUDE THE LAUNDRY ROOM NUMBER ON THE DETAIL AND |
| | SUBMIT A COMPLETE WATER RISER FOR THE LAUNDRY. |
| | 56) ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS. 2014 FPC |
| | SEC. 1002.4. |
| | 57) SHT. P4.10 - SUPPLY THE TONS OF REFRIGERANT PER |
| | RISER. THE SIZING OF THE CONDENSATE RISERS SHALL COMPLY |
| | WITH FPC TABLE 314.2.2. |
| | 58) THE FLOOR DRAINS RECEIVING THE DISCHARGE FROM THE |
| | ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS. |
| | 2014 FPC SEC.1002.4. |
| | |
| | NOTE: THE BUILDING CODE REQUIREMENTS FOR THE POOL |
| | EQUIPMENT ROOM WILL BE REVIEWED WHEN THE POOL PLANS ARE |
| | SUBMITTED. |
| | |