| 2016-08-05 16:30:41 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16061312 |
| | W. P. B. PERMIT: 15031312 |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 1) SHEET 046-A2-5-3 IN STAIRWELL # 4 A 2 HOUR VERTICAL |
| | EXIT ENCLOSURE. THE 5TH FLOOR REFLECTIVE CEILING PLAN |
| | INDICATES A DROPPED PORTION OF THE STAIRWELL CEILING |
| | WITH A 2 HOUR FIRE RATED ENCLOSURE. SHEET 144-A9-4-1 |
| | STAIR DETAIL # 6 ALSO SHOWS THE 2 HOUR SHAFT WALL / |
| | DROPPED CEILING ASSEMBLY BUT WITH A 2 HOUR FIRE RATED |
| | ACCESS PANEL. SHEET 148-A10-1 DETAIL 14 SHOWS A BLOW UP |
| | SECTION OF THE RATED SHAFT WALL/ DROPPED CEILING |
| | ASSEMBLY. |
| | |
| | WHAT THE PLANS DO NOT PROVIDE IS WHAT IS LOCATED ABOVE |
| | THE 2 HOUR SHAFT WALL ASSEMBLY THAT REQUIRES ACCESS? |
| | PLEASE REVIEW THE 2010 FBC-B 1022.5 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT |
| | STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR REQUIRED |
| | EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR |
| | INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER |
| | PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE |
| | DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY |
| | SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED |
| | IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO |
| | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT |
| | STAIRWAYS. |
| | |
| | 2) PLEASE ALSO REFER TO THE MECHANICAL REVIEW, IN |
| | REGARDS TO SHEET M2-6-1 SEE CODE SECTION 1104.2 |
| | INDICATE THE TYPE AND AMOUNT OF REFRIGARATION IN THE |
| | SYSTEMCONTAINED IN THENEW MECHANICAL ROOM. FIRE RATED |
| | MACHINERY ROOMS MAYBE REQUIRED AND ADDITIONAL |
| | REQUIREMENTS PER 1104 & 1105 MAYBE APPLICABLE TO THE |
| | INSTALATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |