| Plan Review Notes For Permit 16061412 |
| Permit Number |
16061412 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-29 06:48:51 | 1) SIZE THE RISER TO THE GRILL ON THE PLANS. | | | 2) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE COPPER | | | PIPE OR REFERENCE THE TABLE ON BOTH SETS OF PLANS. IF | | | YOU ARE USING TABLE 402.4 (9), A 1/2 INCH LINE CARRIES | | | 47,000 BTU'S. THE LINES ARE UNDERSIZED. | | | 3) THE APPLIANCE SPEC SHEETS DO NOT SHOW THAT THE | | | APPLIANCES ARE LISTED AND LABELED PER FGC SEC.301.3. | | | SUBMIT SPECIFICATIONS THAT SHOW THE APPLIANCES ARE | | | LISTED AND LABELED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|