| 2016-11-23 14:01:12 | |
| | 11/28/16 TALKED AND E-MAILED COMMENTS TO PAULINA |
| | MARTINENGO. WAITING FOR RESPONSE IF PROVISO IS |
| | PREFERRED AT THIS TIME. |
| | |
| | |
| | |
| | NOTE; |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. REQUESTED |
| | INFORMATION MAY BE SUBMITTED AFTER THE PERMIT IS ISSUED |
| | BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. |
| | REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF |
| | PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | |
| | |
| | |
| | 1- REVISE PLANS SHOWING THE NUMBER OF FLOOD VENTS |
| | SPECIFIED ON THE-ELEVATION CERTIFICATE. REVISE FLOOR |
| | PLANS AND EXTERIOR ELEVATIONS SHOWING THE EXACT |
| | LOCATION. NOTE: FLOOD VENTS NEED TO BE BELOW THE FLOOD |
| | ELEVATION. |
| | |
| | 2- ELEVATION CERTIFICATE SUBMITTED WAS NOT SEALED. IT |
| | NEEDS TO HAVE THE SURVEYOR'S SEAL AS REQUIRED BY |
| | CHAPTER 472 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | 3- NEW COMMENT: |
| | ROOF MATERIAL WAS CHANGED FROM METAL ROOF TO CONCRETE |
| | TILE. ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING |
| | AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY NUMBER AND SIZE OF |
| | SCREWS. IF SPECIFYING ADHESIVE THEN PROVIDE PRODUCT |
| | APPROVAL FOR THE ADHESIVE LISTED IN THE ROOF TILE |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLOOD VENTS AS SPECIFIED ON PLANS. |
| | |
| | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVE. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW ABOVE PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | IMPORTANT: |
| | (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING |
| | CONSTRUCTION. NOTE: COORDINATE ALL ELEVATION |
| | CERTIFICATES WITH SAMANTHA HILL AT [email protected] OR |
| | (561)805-6724 TO AVOID CONFLICTS OR DELAYS. |
| | (2) SUBMIT SHOP DRAWINGS FOR THE DESIGNED FLOOR SYSTEM, |
| | HANDRAIL AND GUARDRAILS. NOTE: PACKAGES TO BE APPROVED |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | ********************************** |
| | |
| | RE: FW: RANSOM--BUILDING COMMENTS |
| | |
| | FARID ABUGATTAS |
| | TO: |
| | CAROLINE KOONS FORREST, JGOMEZ |
| | 11/28/2016 01:42 PM |
| | |
| | |
| | GOOD AFTERNOON JULIO, |
| | I REALIZED THAT MY NOTES WERE NOT PROPERLY UPDATED TO |
| | REFER TO THE SOILS REPORT. |
| | I WILL BE SUBMITTING THE ATTACHED SHEET SIGNED AND |
| | SEALED ORIGINAL WHICH ADDRESSES THE FACT THAT WE |
| | RE-DESIGNED THE FOUNDATION WITH 2000 PSF. YOU SHOULD |
| | HAVE RECEIVED FROM THE APPLICANT A CLOUDED S1 WITH THE |
| | ENLARGED FOOTINGS. |
| | YOU SHOULD HAVE RECEIVED AS WELL THE SIGNED AND SEALED |
| | LETTER WITH MY STATEMENT APPROVING THE PRODUCT |
| | APPROVALS AS WELL. |
| | PLEASE LET ME KNOW IF ADDITIONAL INFORMATION IS NEEDED |
| | FROM ME. |
| | |
| | THANK YOU, |
| | |
| | |
| | NOTE: IF YOU SEND US AN EMAIL AND DON'T GET A |
| | CONFIRMATION RECEIPT WITHIN 4 HOURS, WE MAY NOT HAVE |
| | RECEIVED IT, CALL US PLEASE. |
| | |
| | |
| | FARID ABUGATTAS, STRUCTURAL ENGINEER, FL P.E. # 72471 |
| | |
| | COORDINATE VIA GMAIL CHAT: [email protected] |
| | WWW.PROJECTCLASSIC.COM/INSURANCE.PDF |
| | |
| | |
| | PHONE LINES: |
| | * NEW PROJECTS: (954) 667 - 7803 |
| | * ACCOUNTING: (813) 516-4271 |
| | * PROJECT STATUS CHECKS / PLANS REQUESTS: (561) 544 - |
| | 7397 |
| | * INSPECTION REQUESTS: (760) 651 - 2227 |
| | * CLASSIC T: (954) 381 9239 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |