Plan Review Notes
Plan Review Notes For Permit 16061387
Permit Number 16061387
Review Stop E
Sequence Number 2
Notes
Date Text
2016-10-20 09:09:302ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 111 RUSSLYN DRIVE
 DESCRIPTION: CONSTRUCTION OF NEW SFR
 MASTER PERMIT: 16061387
  
 DUE TO THE LACK OF A NARRATIVE I HAD TO CONDUCT A
 COMPLETE REVIEW OF THE SUBMITTED ELECTRICAL PLANS.
 BELOW ARE THE DEFICIENCIES NOTED AS A RESULT OF THIS
 REVIEW.
  
 SHEET E0.1
 1. GENERAL ELECTRICAL NOTES 2: SECTION 107.2.1 OF THE
 WPB CITY AMENDMENTS TO THE FBC-B STATES THAT THE
 DRAWINGS SHALL INDICATE THE APPLICABLE DESIGN CODE.
 (NEC 2011/FBC-RE 2014).
 2. CORRECT LIGHTING ENERGY CONSERVATION BLOCK NOTE
 FBC-R404.1 LIGHTING EQUIPMENT (MANDATORY). A MINIMUM OF
 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS.
 3. CORRECT CONSTRUCTION ELECTRICAL NOTE 11: ACCORDING
 TO NEC 620.24 A LIGHT IN THE ELEVATOR PIT IS REQUIRED.
 (AFTER THE REVIEW I NOTICED THAT THERE ISN?T AN
 ELEVATOR ON THIS JOB. THIS IS JUST FYI)
 SHEET E1.1
 4. FBC-R REQUIRES THAT THERE BE MECHANICAL VENTILATION
 IN POWDER ROOM 102 WHENEVER THE ROOM IS OCCUPIED.
 THEREFORE, THE EXHAUST FAN SHALL BE CONNECTED TO THE
 LIGHT SWITCH TO COME ON SIMULTANEOUS WITH THE LIGHT.
 5. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE OUTSIDE THE
 ATTIC IN A VISIBLE LOCATION AND HAVE A PILOT LIGHT TO
 AVOID THE ATTIC LIGHT BEING LEFT ON INADVERTENTLY.
 6. NEC 210.52 HAS SPECIFIC OUTLET PLACEMENT
 REQUIREMENTS AND THIS INCLUDES THE MUD ROOM 119.
 SHEET E1.2
 7. TOILET ROOM 205 HAS THE SAME ISSUE ADDRESSED IN
 COMMENT 4 ABOVE.
 SHEET E3.1
 8. PLEASE EXPLAIN HOW YOU ARRIVED AT YOUR HVAC LOADS IN
 THE CALCS. THE FIGURES DO NOT MATCH THE ENERGY CALCS OR
 THE NUMBERS ON THE MECHANICAL PAGE.
 SHEET E4.1
 9. THE RISER DIAGRAM AS SHOWN ON THE PLANS REQUIRES
 THAT THE ATS BE SERVICE ENTRANCE RATED AND THUS SPECS
 ON THE PROPOSED ATS SHALL ACCOMPANY YOUR RESUBMITTAL.
 10. THE RELATION BETWEEN THE PANEL SCHEDULES AND THE
 LOAD CALCS DO NOT MAKE SENSE TO ME. PLEASE
 SIMPLIFY/CLARIFY THIS FOR ME.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER