| 2016-08-16 11:31:36 | 1ST REVIEW FBC-2014 RESIDENTIAL |
| | PERMIT #16061387 |
| | 8/16/16 |
| | |
| | 1) PROVIDE THE MANUAL J WORKSHEETS- SUMMARY |
| | CALCULATIONS ARE NOT ACCEPTABLE PER SECTION R403.6.1 |
| | FBC ENERGY CONSERVATION- EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. |
| | |
| | 2) THE AC CALCULATIONS DO NOT SHOW CFMS FOR OUTDOOR |
| | VENTILATION AIR DATA, HOWEVER THE PLAN SHOWS O/A DUCTS |
| | SUPPLYING AH-2, 4, 5, & 6. PLEASE PROVIDE O/A |
| | CALCULATIONS, AND INDICATE IF O/A WILL BE PROVIDED FOR |
| | THE FIRST FLOOR ROOMS AND SPACES SERVED BY AH-1 & 2, OR |
| | IF NATURAL VENTILATION WILL BE THE METHOD. |
| | |
| | 3) INDICATE THE TYPE OF O/A DUCT TO BE USED. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE, |
| | AND THE KITCHEN EXHAUST HOOD AND EXHAUST SYSTEM- SEE |
| | SECTIONS M1901.2 & M1503. INDICATE HOW THE MAKEUP AIR |
| | SYSTEM WILL BE LINKED TO THE EXHAUST SYSTEM. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE AC |
| | SYSTEMS INCLUDING INSTALLATION DETAILS FOR THE |
| | CONDENSER UNITS- SEE SECTIONS M1401.1, M1403.1, M1401.4 |
| | AND M1305.1.4.1 FBC-14 RESIDENTIAL. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER |
| | AND PROVIDE MAKEUP AIR AND CALCULATIONS IF APPLICABLE- |
| | SEE SECTION 504.5 FBC-14 MECHANICAL. |
| | |