| 2016-07-26 12:04:02 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | GAS COMMENTS: | | | | | | 1. SHOW LENGTH OF EACH SECTION OF PIPE ON THE RISER | | | DIAGRAM. PER WPB AMEND. TO FBC 107.2.1 | | | | | | 2. IT APPEARS THAT THE .5LB SYSTEM FOR THE GENERATOR | | | AND POOL HEATER IS UNDER SIZED I CANNOT BE SURE UNTIL I | | | HAVE THE LENGTH OF OF EACH PIECE OF PIPE. PER WPB | | | AMEND. TO FBC 107.2.1 | | | | | | | | | 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. |
|