| 2016-07-14 16:11:40 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. THE SCOPE OF THIS REVISION EXCLUDES BOTH, THE |
| | ELECTRICAL EQUIPMENT AND EQUIPOTENTIAL BONDING FOR THE |
| | POOL AND THE GENERATOR, BOTH OF WHICH SHALL BE |
| | INSTALLED UNDER A SEPARATE PERMIT. |
| | 2. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS. |
| | BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| | CEILING BOXES ON PAGE. |
| | 3. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 4. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. |
| | 5. FBC-RE3901.11/NEC 210.52(I): FOYERS THAT ARE NOT |
| | PART OF A HALLWAY AS DESCRIBED IN THIS CODE AND THAT |
| | HAVE AN AREA THAT IS GREATER THAN 60 SQ. FT. SHALL HAVE |
| | A RECEPTACLE LOCATED IN EACH WALL SPACE THAT IS GREATER |
| | THAN 3 FT. AND UNBROKEN BY DOORWAY. FLOOR TO CEILING |
| | WINDOWS OR SIMILAR OPENINGS. SEE FOYER 101. |
| | 6. FBC-RE3901.6 NEC 210.52(D) BATHROOMS. IN DWELLING |
| | UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE |
| | OF EACH BASIN. SEE GUEST BATHROOM 111. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |