| 2016-07-26 12:43:25 | 2ND REVIEW MECHANICAL | | | PERMIT #16061357 | | | 7/26/16 | | | | | | 1) SHEET 2: THE PLAN IS INDICATING 1850 CFMS OF SUPPLY | | | AIR FOR THE EXISTING 4-TON SYSTEM. PLEASE SUBMIT A | | | MANUFACTURER'S DATA SHEET FOR THE SYSTEM INDICATING | | | MAXIMUM CFMS OF SUPPLY AIR. | | | | | | 2) SHEET 2: THE PLAN DOES NOT CLEARLY INDICATE A MEANS | | | OF RETURN AIR TO THE AIR HANDLER- NEITHER A DOOR OR | | | RETURN AIR GRILL ARE SHOWN AT THE MECHANICAL CLOSET. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|