| 2016-07-25 14:03:22 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: CONDO RENOVATION |
| | JOB ADDRESS: 400 N. FLAGLER DR. |
| | DESCRIPTION: RENO OF CONDO AS INDICATED ON THE PERMIT |
| | APPLICATION |
| | MAST. PERMIT: 16061357 |
| | REVISION: |
| | |
| | CONDITIONAL APPROVAL AS FOLLOWS: |
| | |
| | 1. THE SCOPE OF THE ELECTRICAL UPGRADE IS NOT DEFINED |
| | ON THE SUBMITTED PLANS, THEREFORE THE CONDITIONAL |
| | APPROVAL HEREIN IS SUBJECTED TO THE APPROVAL OF THE |
| | FIELD INSPECTOR. |
| | 2. THE OUTLET SPACING AS INDICATED ON THE SUBMITTED |
| | DRAWINGS DO NOT COMPLY WITH MINIMUM CODE REQUIREMENTS, |
| | THEREFORE ELECTRICAL CONTRACTOR SHALL PLACE OUTLETS AS |
| | REQUIRED BY CODE AND NOT LIMIT ITSELF TO THE MARKINGS |
| | ON THE PLANS. |
| | 3. THE FBC-RE CODE REQUIRES THAT A MINIMUM OF 75% OF |
| | THE LAMPS IN PERMANENTLY INSTALLED FIXTURES BE OF THE |
| | HIGH-EFFICIENCY TYPE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |