| Plan Review Notes For Permit 16061357 |
| Permit Number |
16061357 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-28 11:05:32 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16061357 | | | 6/28/16 | | | | | | 1) REFER TO SECTION 107.2.1 WPB AMENDMENTS TO THE FBC | | | AND PROVIDE PLANS WITH CLEARER PRINT- SOME OF THE | | | MEASUREMENTS AND NOTES ARE BARELY LEGIBLE. | | | | | | 2) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN FOR | | | MECHANICAL ALTERATIONS- THE PLAN DOES NOT INDICATE | | | WHICH DUCTS ARE EXISTING, REPLACED, OR RELOCATED. | | | SIMPLE SYMBOLS SUCH AS (E) EXISTING, (N) NEW, OR (RE) | | | RELOCATED WOULD BE HELPFUL. | | | | | | 3) PROVIDE AN AIR DEVICE SCHEDULE LISTING THE MAKES AND | | | MODELS OF THE DIFFUSERS AND GRILLS. PLEASE NOTE THAT | | | THE 48-2 DIFFUSER SUPPLING 260 CFM'S TO THE BEDROOM IS | | | UNDERSIZED. | | | | | | 4) INDICATE THE MAKE AND MODEL OF THE EXISTING AC | | | SYSTEM AND IT'S HEATING AND COOLING CAPACITY. | | | | | | 5) THE AIR HANDLER CLOSET DOOR WHICH IS SPECIFIED AS A | | | WOOD LOUVERED DOOR SHALL BE NON-COMBUSTIBLE PER SECTION | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|