2016-06-29 17:05:191ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. CONTRARY TO THE MARKINGS ON THE SUBMITTED PLANS, ALL
 WORK SHALL BE MADE COMPLIANT TO THE 2011 EDITION OF THE
 NEC & THE 5TH EDITION OF THE FBC 2014 EDITION. NOT THE
 2010 FBC & 2008 NEC AS INDICATED.
 2. IN ADDITION TO THE LIGHTING PLAN YOU SHALL SUBMIT A
 POWER PLAN SHOWING THE PLACEMENT OF ALL RECEPTACLES
 EXISTING OR OTHERWISE. OUTLETS SHALL BE MARKED AS
 EXISTING, NEW OR EXISTING TO BE RELOCATED ETC.
 3. IN ADDITION TO THE PANEL SCHEDULE, YOU ARE TO SUBMIT
 LOAD CALCS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  