| Plan Review Notes For Permit 16061357 |
| Permit Number |
16061357 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-29 17:05:19 | 1ST ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | 1. CONTRARY TO THE MARKINGS ON THE SUBMITTED PLANS, ALL | | | WORK SHALL BE MADE COMPLIANT TO THE 2011 EDITION OF THE | | | NEC & THE 5TH EDITION OF THE FBC 2014 EDITION. NOT THE | | | 2010 FBC & 2008 NEC AS INDICATED. | | | 2. IN ADDITION TO THE LIGHTING PLAN YOU SHALL SUBMIT A | | | POWER PLAN SHOWING THE PLACEMENT OF ALL RECEPTACLES | | | EXISTING OR OTHERWISE. OUTLETS SHALL BE MARKED AS | | | EXISTING, NEW OR EXISTING TO BE RELOCATED ETC. | | | 3. IN ADDITION TO THE PANEL SCHEDULE, YOU ARE TO SUBMIT | | | LOAD CALCS. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|