| Plan Review Notes For Permit 16061354 |
| Permit Number |
16061354 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2017-01-24 17:09:27 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16061354 | | | 1/24/17 | | | | | | 1) THERE APPEARS TO BE A CONFLICT IN THE PLANS | | | REGARDING THE MAKEUP AIR SYSTEM FOR THE HOOD EXHAUST. | | | BOTH A STRAIGHT SUPPLY FAN AND TWO 5-TON 100% O/A | | | SYSTEMS ARE SHOWN PROVIDING MAKEUP AIR TO THE HOOD: | | | PLEASE CLARIFY WHICH SYSTEM IS TO BE USED. | | | | | | 2) PROVIDE HOOD HANGING DETAILS. | | | | | | 3) ALTHOUGH GLASS IS NOT A COMBUSTIBLE MATERIAL, PLEASE | | | PROVIDE SUFFICIENT CLEARANCE FROM THE HOOD TO THE GLASS | | | PER THE UL LISTING AND MANUFACTURER'S SPECIFICATIONS.- | | | SECTION 304.1 | | | | | | 4) PLEASE REMOVE THE VOIDED PAGES FROM THE PLAN SETS | | | AND RETAIN THEM IN THE FILE FOR REFERENCE. | | | | | | 5) PLEASE ASSEMBLE THE M2 AND M3 PLAN SHEETS SO THEY | | | CAN BE REVIEWED ENTIRELY. CURRENTLY, THE LEFT MARGINS | | | ARE CUT-OFF. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|