| Plan Review Notes For Permit 16061354 |
| Permit Number |
16061354 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-09-21 08:14:09 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16061354 | | | 9/21/16 | | | | | | 1) REFER TO COMMENT #8 FROM THE 1ST REVIEW AND PROVIDE | | | COMPLETE ENGINEERING FOR INSTALLATION OF THE ROOFTOP | | | MECHANICAL EQUIPMENT INCLUDING: A) DETAILS FOR MOUNTING | | | AND ANCHORING THE ROOF FANS AND FAN CURBS. B) DETAILS | | | FOR ROOFTOP FASTENING AND ANCHORING THE MUA DUCTWORK | | | AND SUPPORT BRACES. | | | | | | 2) REFER TO COMMENT #11 FROM THE 1ST REVIEW AND PROVIDE | | | CALCULATIONS FOR SIZING THE MUA UNIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | THANK YOU, | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|