Plan Review Notes
Plan Review Notes For Permit 16061354
Permit Number 16061354
Review Stop M
Sequence Number 2
Notes
Date Text
2016-07-22 15:16:182ND REVIEW MECHANICAL
 PERMIT #16061354
 7/22/16
  
 1) THE REQUESTED EQUIPMENT SCHEDULES FOR THE EXHAUST
 AND MAKEUP AIR FANS HAVE NOT BEEN PLACED ON THE PLANS.
  
 2) THE REQUESTED AIR VELOCITY CALCULATION WAS PERFORMED
 USING A 9 X 29" DUCT, HOWEVER THE GREASE EXHAUST DUCT
 SIZE IS INDICATED TO BE 16 X 16".
  
 3) A 2" CLEARANCE FOR THE HOOD TO THE FRONT EXTERIOR
 WALL IS SHOWN, HOWEVER AN 18" CLEARANCE TO COMBUSTIBLES
 IS REQUIRED. PLEASE SEE SECTION 507.9 AND EXCEPTION,
 AND LABEL THE WALL AS EITHER COMBUSTIBLE OR
 NON-COMBUSTIBLE AND INDICATE WHAT THE WALL MATERIALS
 ARE.
  
 4) M-1: IT APPEARS THAT THE ROOF FANS ARE WITHIN 10' TO
 THE ROOF EDGE WHICH REQUIRES GUARDS TO BE INSTALLED PER
 SECTION 304.11- REVISE THE PLAN ACCORDINGLY.
  
 5) COMMENTS #8, 9, 11, & 12 FROM THE 1ST REVIEW STILL
 EXIST. I AM REPRINTING THOSE COMMENTS BELOW. PLEASE
 SUBMIT CORRECTED PLANS ACCOMPANIED BY A RESPONSE
 NARRATIVRE FROM THE DESIGN PROFESSIONAL.
  
 1ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061354
 6/30/16
  
 8) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING OF THE
 FANS AND CURBS TO THE ROOF STRUCTURE- SECTION 301.15.
 PLEASE INCLUDE NOA'S FOR THE ROOF FANS WITH A SHOP
 DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF RECORD.
  
 9) PROVIDE A HOOD HANGING DETAIL.
  
 11) REFER TO SECTION 508.1.1 AND SHOW COMPLIANCE FOR
 MAKEUP AIR TEMPERATURE: THE TEMPERATURE DIFFERENTIAL
 BETWEEN MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE
 SHALL NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT
 WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP
 AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 12) PROVIDE AN AIR BALANCE CALCULATION.
  