Plan Review Notes
Plan Review Notes For Permit 16061354
Permit Number 16061354
Review Stop G
Sequence Number 2
Notes
Date Text
2016-08-02 06:14:191) SHOW ON THE PLANS HOW THE REQUIREMENTS FOR
 COMBUSTION AIR FOR THE GAS APPLIANCES WILL BE MET PER
 2014 FGC SEC.304.1, 304.5.1. YOU HAVE SHOWN ON THE
 PLANS HOW MUCH COMBUSTION AIR IS REQUIRED ( 133 CFM)
 BUT YOU HAVE NOT SHOWN HOW IT IS GOING TO BE SUPPLIED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) IF THE REQUIREMENTS FOR COMBUSTION AIR WILL BE
 PROVIDED BY THE BUILDING'S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR PER THE 2014 FBC-FUEL GAS SEC. 304.9.3.
 3) WHERE ALL COMBUSTION AIR IS PROVIDED BY A MECHANICAL
 AIR SUPPLY SYSTEM, THE SYSTEM SHALL COMPLY WITH 2014
 FBC-FUEL GAS SECS.304.9, 304.9.1, 304.9.2.
 4) SUBMIT DOCUMENTATION FOR THE GAS EQUIPMENT THAT
 SHOWS THE EQUIPMENT IS LISTED AND LABELED PER THE 2014
 FBC-FUEL GAS SEC. 301.3.
 5) THE NOTE ON THE GAS RISER CALLS OUT THE TOTAL RUN AS
 ONE-HUNDRED FEET BUT THE MEASUREMENTS ON THE GAS RISER
 ADD UP TO 120 FEET. CLARIFY.
 6) SIZE THE SECTIONS OF PIPE DOWNSTREAM OF THE AUTO
 SHUTOFF VALVE AND THE LINE SUPPLYING THE APPLIANCES. IS
 IT ALSO ONE INCH? CLARIFY.
 7) THERE ARE TWO SHEETS LABELED "P". VOID THE OLD
 SHEET.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  