| 2016-08-02 06:14:19 | 1) SHOW ON THE PLANS HOW THE REQUIREMENTS FOR | | | COMBUSTION AIR FOR THE GAS APPLIANCES WILL BE MET PER | | | 2014 FGC SEC.304.1, 304.5.1. YOU HAVE SHOWN ON THE | | | PLANS HOW MUCH COMBUSTION AIR IS REQUIRED ( 133 CFM) | | | BUT YOU HAVE NOT SHOWN HOW IT IS GOING TO BE SUPPLIED. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) IF THE REQUIREMENTS FOR COMBUSTION AIR WILL BE | | | PROVIDED BY THE BUILDING'S MECHANICAL VENTILATION | | | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED | | | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED | | | VENTILATION AIR PER THE 2014 FBC-FUEL GAS SEC. 304.9.3. | | | 3) WHERE ALL COMBUSTION AIR IS PROVIDED BY A MECHANICAL | | | AIR SUPPLY SYSTEM, THE SYSTEM SHALL COMPLY WITH 2014 | | | FBC-FUEL GAS SECS.304.9, 304.9.1, 304.9.2. | | | 4) SUBMIT DOCUMENTATION FOR THE GAS EQUIPMENT THAT | | | SHOWS THE EQUIPMENT IS LISTED AND LABELED PER THE 2014 | | | FBC-FUEL GAS SEC. 301.3. | | | 5) THE NOTE ON THE GAS RISER CALLS OUT THE TOTAL RUN AS | | | ONE-HUNDRED FEET BUT THE MEASUREMENTS ON THE GAS RISER | | | ADD UP TO 120 FEET. CLARIFY. | | | 6) SIZE THE SECTIONS OF PIPE DOWNSTREAM OF THE AUTO | | | SHUTOFF VALVE AND THE LINE SUPPLYING THE APPLIANCES. IS | | | IT ALSO ONE INCH? CLARIFY. | | | 7) THERE ARE TWO SHEETS LABELED "P". VOID THE OLD | | | SHEET. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|