| 2016-06-30 14:32:00 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16061354 |
| | 6/30/16 |
| | |
| | 1) THE M PLAN HAS A MIAMI BEACH ADDRESS ON IT- PLEASE |
| | CORRECT. |
| | |
| | 2) PROVIDE EQUIPMENT SCHEDULES FOR THE EXHAUST AND |
| | MAKEUP AIR FANS. |
| | |
| | 3) PROVIDE AN AIR VELOCITY CALCULATION FOR THE EXHAUST |
| | DUCT- SECTION 506.3.4. |
| | |
| | 4) REFER TO SECTION 507.9 AND INDICATE THE REQUIRED |
| | CLEARANCES FOR THE GREASE HOOD INCLUDING WHERE IT IS |
| | SHOWN BUTTING UP TO THE FRONT EXTERIOR WALL- SECTION |
| | 507.9. |
| | |
| | 5) SHOW THE VERTICAL DISTANCE FROM THE THE LOWER LIP OF |
| | THE HOOD AND TO THE TOP HORIZONTAL SURFACE OF THE |
| | APPLIANCE- SECTION 507.12. |
| | |
| | 6) PROVIDE A FRONT VIEW DRAWING OF THE HOOD THAT SHOWS |
| | THE GREASE EXHAUST AND MAKEUP AIR DUCT RUNS, AND |
| | INCLUDES THE TYPE AND SIZE OF DUCT, AND THE REQUIRED |
| | CLEARANCES TO COMBUSTIBLES- SEE SECTION 506.3.11. |
| | PLEASE SEE SECTION 506.3.11.2 FOR FIELD APPLIED GREASE |
| | ENCLOSURES AND INDICATE THE MAKE AND MODEL OF THE DUCT |
| | WRAP ON THE PLAN AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS, |
| | |
| | 7) PROVIDE A ROOF PLAN SHOWING THE REQUIRED CLEARANCE |
| | DISTANCE FROM THE EXHAUST AND MAKE UP AIR FANS TO THE |
| | ROOF EDGES- SECTION 304.11 |
| | |
| | 8) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING OF THE |
| | FANS AND CURBS TO THE ROOF STRUCTURE- SECTION 301.15. |
| | PLEASE INCLUDE NOA'S FOR THE ROOF FANS WITH A SHOP |
| | DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF RECORD. |
| | |
| | 9) PROVIDE A HOOD HANGING DETAIL. |
| | |
| | 10) REFER TO SECTION 507.11 AND SHOW THE LOCATIONS OF |
| | AND PROVIDE DETAILS FOR REQUIRED GREASE FILTERS. PLEASE |
| | NOTE THAT THE FILTERS SHALL BE LISTED AND LABELED IN |
| | ACCORDANCE WITH UL 1046. |
| | |
| | 11) REFER TO SECTION 508.1.1 AND SHOW COMPLIANCE FOR |
| | MAKEUP AIR TEMPERATURE: THE TEMPERATURE DIFFERENTIAL |
| | BETWEEN MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE |
| | SHALL NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT |
| | WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| | AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 12) PROVIDE AN AIR BALANCE CALCULATION. |
| | |