| Plan Review Notes For Permit 16061352 |
| Permit Number |
16061352 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-05 07:48:21 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16061353 | | | 7/5/16 | | | | | | 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | | RETURN AIR SYSTEMS OF AC SYSTEMS 1 & 2- SECTION | | | 606.2.1. PLEASE NOTE THAT MANUFACTURER'S SPECIFICATIONS | | | TYPICALLY INDICATE THAT 5-TON SYSTEMS HAVE CAPACITIES | | | EXCEEDING 2000 CFMS. | | | | | | 2) M1.1: PROVIDE THE CLEARANCE DISTANCES FOR THE O/A | | | INTAKES AS REQUIRED BY SECTION 401.4, ITEMS 1-4. | | | | | | 3) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION OF THE EXTERIOR CONDENSERS, AND COMPLETE | | | DETAILS FOR ANCHORING THE UNITS TO THE CONCRETE PADS- | | | LENGTH OF THE 1/4" BOLT, AND TYPE AND SIZE OF CLIP | | | FASTENERS- SECTION 301.15. | | | | | | 4) A-1.1 & M0.1: DOORS A101 & B101 MUST BE | | | NON-COMBUSTIBLE- SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|